Analog Inputs

24

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

Configuration #3:

[Anlg In Config], bit 0 = “1” (Current)

[Speed Ref A Sel] = “Analog In 1”

[Speed Ref A Hi] = 60 Hz

[Speed Ref A Lo] = 0 Hz

[Analog In 1 Hi] = 20 mA

[Analog In 1 Lo] = 4 mA

This configuration is referred to as offset. In this case, a 4-20 mA input signal
provides 0-60 Hz output, providing a 4 mA offset in the speed command.

Configuration #4:

[Anlg In Config], bit 0 = “0” (Voltage)

[Speed Ref A Sel] = “Analog In 1”

[Speed Ref A Hi] = 0 Hz

[Speed Ref A Lo] = 60 Hz

[Analog In 1 Hi] = 10V

[Analog In 1 Lo] = 0V

This configuration is used to invert the operation of the input signal. Here,
maximum input (10 Volts) represents 0 Hz and minimum input (0 Volts)
represents 60 Hz.

Analog Scaling
[Speed Reference A Sel] = “Analog In 1”
[Analog In 1 Hi]
20 mA

[Speed Ref A Hi]
60 Hz

[Analog In 1 Lo]
4 mA

[Speed Ref A Lo]
0 Hz

4

8

12

16

20

6

0

12

18

Output Hertz

Input mA

24

30

36

42

48

54

60