Table 3.6 Fault Register and Check Bit Fault Counter Register

Usage for a

Analog Rail Module

Bit 4: Analog Channel 2 Input Over-Range

Bit 5: Analog Channel 2 Input Under-Range

Bit 6: Analog Channel 3 Input Over-Range

Bit 7: Analog Channel 3 Input Under-Range

Bit 8: No device plugged into a configured port

Bit 9: Bad ID code: device other than a rail is plugged into the port

Bit 10: PMI interface is not ready

Port 0 Check Bit Fault Counter Register

Port 1 Check Bit Fault Counter Register

3.2

Communication Status Registers

(Registers

080-I 089)

The

Communication Registers display the status of the fiber-optic communications

between the UDC module and the PMI. Two consecutive errors will be indicated by a communication

fault and the drive will stop. Refer to register

202, bit 15 for more information. Note that the

communication

status

registers are for system use only and can only be monitored. They cannot be

defined during configuration for access within the application task. The status of these registers will

be retained after a Stop All.

080

UDC Module Ports A/B Status Register

The UDC Module Ports A/B Status register contains bits which describe any errors or warnings re-

ported on the UDC module related to

communication on Port A and Port These bits are

latched when set and will remain set until a fault reset or warning reset is issued.

Bit: 0
Hex Value: 0001

H

Sug. Var. Name:

N/A

Range: N/A

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

Description:

The Invalid Receive Interrupt bit is set when the interrupt generated by the Universal

Serial Controller (USC) is not properly marked. Two consecutive errors of this type will result in a
communication fault.