Meter Port 1

1002

UDC Module Meter Port 1 Register Number Register

Hex Value:

N/A

Sug. Var. Name:

N/A

Range:

N/A

Access:

Read/Write

UDC Error Code:

N/A

LED:

N/A

Description:

UDC register number

(o-2044)

to be mapped to meter port 1.

1003

UDC Module Meter Port 1 Bit Number Register

Hex Value:

N/A

Sug. Var. Name:

N/A

Range:

N/A

Access:

Read/Write

UDC Error Code:

N/A

LED:

N/A

Description:

Bit number of the UDC register specified in register 1002 that is to be mapped to port 1.

Enter a value of 100 (bit 00) to 115 (bit 15) as required. Enter a value of zero if all of the register’s bits

are to be displayed.

1004

UDC Module Meter Port 1 Maximum Value Register

Hex Value:

N/A

Sug. Var. Name:

N/A

Range:

N/A

Access:

Read/Write

UDC Error Code:

N/A

LED:

N/A

Description:

Set this register to the number that will represent + 1 OV. The maximum allowable value

is 32767.

1005

UDC Module Meter Port 1 Minimum Value Register

Hex Value:

N/A

Sug. Var. Name:

N/A

Range:

N/A

Access:

Read/Write

UDC Error Code:

N/A

LED:

N/A

Description:

Set this register to the number that will represent -1 OV. The minimum allowable value

is -32768.

3-44