Interlock Register (Continued)

Bit: 2

Hex Value: 0004H
Sug. Var. Name:

WCI_GAN@

Range:

N/A

Access:

Read Only

UDC Error Code:

N/A

LED:

N/A

Description:

The CML Gains Not Loaded bit is set if the armature gains are zero, i.e., have not been

auto-tuned for, or if a UDC task containing the pre-defined gain variables has not been loaded.

Bit: 3
Hex Value: 0008H
Sug. Var. Name:

WCI_FLT@

Range:

N/A

Access:

Read Only

UDC Error Code:

N/A

LED:

N/A

Description:

The CML Faults Need to be Reset bit is set if previous armature faults (register

202/1 202) have not been cleared.

Bit: 4
Hex Value:

001 OH

Sug. Var. Name:

WCI_RPI@

Range:

N/A

Access:

Read Only

UDC Error Code:

N/A

LED:

N/A

Description:

The Run Permissive Input is Missing bit is set if the run permissive input on the Resolver

& Drive l/O module is not on.

Bit: 5
Hex Value: 0020H
Sug. Var. Name:

WCI_FNR@

Range:

N/A

Access:

Read Only

UDC Error Code:

N/A

LED:

N/A

Description:

The Field Not Ready bit is set if the single-phase field is not on. Note that the CML can-

not be executed if the field is not on.

Bit: 6
Hex Value: 0040H

Sug. Var. Name:

WCI_FNA@

Range:

N/A

Access:

Read Only

UDC Error Code:

N/A

LED:

N/A

Description:

The Field Not Allowed bit is set if the single-phase field is requested when the armature

identification test or the armature alpha test is running.