UDC Test Switch Inputs Register (Continued)

Bit: 2
Hex Value: 0004H

Sug. Var. Name:

SWIT_DN@

Range:

N/A

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

Description:

The Switch Down Input bit is on when the switch is in the down position.

Bit: 8
Hex Value:

01 00H

Sug. Var. Name:

N/A

Range:

N/A

Access:

Read only

UDC Error Code:

N/A

LED: OS

OK on the UDC module

Description:

Status of the Operating System OK LED on the UDC module (0 = Off; 1 = On).

Bit: 9
Hex Value: 0200H

Sug. Var. Name:

N/A

Range:

N/A

Access:

Read only

UDC Error Code:

N/A

LED:

COMM A OK on the UDC module

Description:

Status of the COMM A OK LED on the UDC module (0 = Off; 1 = On).

Bit:

10

Hex Value: 0400H
Sug. Var. Name:

N/A

Range:

N/A

Access:

Read only

UDC Error Code:

N/A

LED:

DRV A FLT on the UDC module

Description:

Status of the Drive A Fault LED on the UDC module (0 = Off; 1 = On).

Bit:

11

Hex Value: 0800H
Sug. Var. Name:

N/A

Range:

N/A

Access:

Read only

UDC Error Code:

N/A

LED:

COMM B OK on the UDC module

Description:

Status of the COMM B OK LED on the UDC module (0 = Off; 1 = On).

Bit: 12
Hex Value: 1

000H

Sug. Var. Name:

N/A

Range:

N/A

Access:

Read only

UDC Error Code:

N/A

LED:

DRV B FLT on the UDC module

Description:

Status of the Drive B Fault LED on the UDC module (0 = Off; 1 = On).

3-41