Rockwell Automation SD3000 Drive Configuration, Programming User Manual
Page 65

Meter Port 2
1008
UDC Module Meter Port 2 Register Number Register
Hex Value:
N/A
Sug. Var. Name:
N/A
Range:
N/A
Access:
Read/Write
UDC Error Code:
N/A
LED:
N/A
Description:
UDC register number (o-2044) to be mapped to meter port 2.
1007
UDC Module Meter Port 2 Bit Number Register
Hex Value:
N/A
Sug. Var. Name:
N/A
Range:
N/A
Access:
Read/Write
UDC Error Code:
N/A
LED:
N/A
Description:
Bit number of the UDC register specified in register 1006 that is to be mapped to port 2.
Enter a value of 100 (bit 00) to 115 (bit 15) as required. Enter a value of zero if all of the register’s bits
are to be displayed.
1008
UDC Module Meter Port 2 Maximum Value Register
Hex Value:
N/A
Sug. Var. Name:
N/A
Range:
N/A
Access:
Read/Write
UDC Error Code:
N/A
LED:
N/A
Description:
Set this register to the number that will represent +10V. The maximum allowable value
is 32767.
1009
UDC Module Meter Port 2 Minimum Value Register
Hex Value:
N/A
Sug. Var. Name:
N/A
Range:
N/A
Access:
Read/Write
UDC Error Code:
N/A
LED:
N/A
Description:
Set this register to the number that will represent - 1 0V. The minimum allowable value
is -32768.
3-45