Appendix a, Continued) – Rockwell Automation SD3000 Drive Configuration, Programming User Manual

Page 84

Advertising
background image

*Appendix A

(Continued)

FEEDBACK REGISTERS (Continued)

300-599

A/B

205/1205 Interlock

Bit

UDC MODULE TEST INPUTS

0 Multiple CML requests

WCI_ILL@

1 Arm. parameters not loaded WCI_CNF@
2 Arm, gains not loaded

WCI_GAN@

3 Arm. faults need to be reset WCI_FLT@
4 Run permissive missing

WCI_RPl@

5 Arm. field not ready

WCI_FNR@

6 Arm. field not allowed

WCI_FNA@

7 M-contactor did not close

WCI_MCR@

8 Multiple field requests

WFI_ILL@

9 Field parameters not

loaded

WFI_CNF@

10 Field gains not loaded

WFI_GAN@

11 Field faults need to

WFI_FLT@

be reset

1000

Switches

Bit

0 UDC pushbutton

UDC_PB@

1 UDC switch UP-position

SWIT_UP@

2 UDC switch DOWN-position SWIT_DN@

LEDs

8 OS OK
9 Comm A OK

10 Drive A fault
11 Comm B OK
12 Drive B fault

METER PORT SETUP

206/1206 AC line voltage feedback

AC_VRMS%

207/1 207 CML feedback

CML_FB%

208/1 208 Arm. current fdbk.

ARM_IFB%

10=1 amp)

209/1209 Arm. voltage fdbk.

(1 =1 volt)

A R M - V F B %

210/1210 Counter-EMF (1 =1 volt)

EMF_VFB%

211/1211 FML feedback (4095=100%)

FML_FB%

212/1 212 Field amps fdbk.

(100=1 amp)

FLD_IFB%

213/1 213 Arm. field voltage feedback FLD_VFB%

214/1214 User analog input

Al%

(-2048 = -lov to

2047 =+10V)

1001

Initiate change in setup (non-zero value)

1002

Port 1 UDC register number (O-2047)

1003

Port 1 bit number (100-115, 0 = all bits)

1004

Port 1 maximum value

1005

Port 1 minimum value

1006

Port 2 UDC register number ( o - 2 0 4 7 )

1007

Port 2 bit number (100-115, 0 = all bits)

1008

Port 2 maximum value

1009

Port 2 minimum value

1010

Port 3 UDC register number (o-2047)

1011

Port 3 bit number (100-115, 0 = all bits)

1012

Port 3 maximum

value

1013

Port 3 minimum value

1014

Port 4 UDC register number (O-2047)

1015

Port 4 bit number (100-115, 0 = all bits)

1016

Port 4 maximum value

1017

Port 4 minimum value

215/1 215 Resolver scan position

(-32768 to 32767)

RES_SCN_POS%

1300-

1599 Application registers updated every Nth

scan - A/B

216/1 216 Resolver strobe position

RES_STR_POS%

(-32768 to 32767)

Application registers

scan - A/B

updated

INTERRUPT STATUS and CONTROL (ISCR)

2000

Interrupt status and control

UDC_ISCR%

Bii
O-l Interrupt line ID
2 Interrupt allocated
4 Interrupt this scan
5 CCLK counting
6

Enable CCLK to backplane*

7 Interrupt enabled
15 Interrupt status

2001

Scans per interrupt

2002

SPI counter

2010

Diagnostic error code

Bit

0 UDC memory failure

*Only bit 6 in register 2000 can be written to by the

programmer. All other bits in register 2000 are read
only.

GAIN VARIABLES*

Current minor loop crossover frequency CML_WCO%

(initial = 200 radians)

Armature resistance

A R M - R %

(1000 = 1 Ohm)

Armature field electrical time constant

ARM_TE%

(10 = 1 msec Te)

Armature threshold current

ARM_CCT%

(10 = 1 amp)

Field minor loop crossover

FML_WCO%

frequency (initial=1 5 radians)

Field resistance

FLD_R%

(10 = 1 Ohm)

Field electrical time constant

FLD-TE%

(1 = 1 msec Tf)

SCR diagnostic gain

SCR-GAN%

(initial = 100)

SCR diagnostic decay rate

SCR_DECAY%

(initial = 99)

SCR diagnostic deadband

SCR_DBAND%

(initial = 10)

SCR diagnostic trip point

SCR_TRIP%

(initial = 1500)

Resolver gain

RES_GAN%

(initial = 0)

Resolver balance

RES_BAL%

(initial = 0)

*Note that the scale and initial values shown for these

variables apply to 3-phase armature regulation and

l-phase field regulation.

A-2