Drive Fault Register

The bits in the Drive Fault register indicate the cause of a drive shutdown. The bits in this register are

latched until they are reset by setting the Fault Reset bit (bit 8) of the Drive Control register
(100/1 100). After turning the Fault Reset bit on, the drive may be re-started after turning the com-
mand bits off and then back on again. If the fault conditions still exist, the identifying bit in this regis-

ter will immediately be set again.

The fault conditions reported in this register result in turning off the drive. The UDC task is not

stopped automatically when a drive fault occurs unless it is specifically instructed to in an application

task. The user must ensure that the AutoMax application task tests register 202/1202 and takes ap-

propriate action if a fault occurs.

Note that the status of this register is also reported in the error log for the task in which the error oc-
curred.

Bit: 0
Hex Value:

0001 H

Sug. Var. Name:

FLT_SCR@

Range:

N/A

Access:

Read Only

UDC Error Code:

1000

LED:

PM FLT on the PMI Processor module

Description:

The Shorted SCR Fault bit will be set if a shorted SCR is detected. Check register

204/1204 to identify the SCR that has shorted.

Bit: 3
Hex Value: 0008H
Sug. Var. Name:

FLT_SYN@

Range:

N/A

Access:

Read Only

UDC Error Code:

1003

LED:

EXT FLT on the PMI Processor module

Description:

The A-C Line Synchronization Fault bit is set when the A-C line voltage is missing for

more than 2 seconds. See register 203/1203, bit 3 for more information.

Bit: 4
Hex Value:

001 OH

Sug. Var. Name:

FLT_IOC@

Range:

N/A

Access:

Read Only

UDC Error Code:

1004

LED:

EXT FLT on the PMI Processor module

Description:

The Instantaneous Overcurrent Fault bit is set when the armature current feedback val-

ue is greater than the Max Current Limit value (plus 75%) entered as a configuration parameter.

Bit: 5
Hex Value: 0020H
Sug. Var. Name:

FLT_CON@

Range:

N/A

Access:

Read Only

UDC Error Code:

1005

LED:

N/A

Description:

The Conduction Timeout Fault bit is set if CM/RUN@ (register 100/1 100, bit 0) is

turned off and discontinuous conduction is not detected within 2 seconds.

3-26