Rockwell Automation SD3000 Drive Configuration, Programming User Manual

Page 48

Advertising
background image

202/1 202 Drive Fault Register (Continued)

Bit:

10

Hex Value: 0400H
Sug. Var. Name:

FLT_OSP@

Range:

N/A

Access:

Read Only

UDC Error Code: 1010
LED:

EXT FLT on the PMI Processor module

Description:

The Overspeed Fault bit is set when the motor’s velocity exceeds the value entered as

the Over Speed Trip (RPM) configuration parameter. This bit is not used if the No Speed Feedback
option is chosen as a configuration parameter.

Bit:

11

Hex Value: 0800H
Sug. Var. Name:

FLT_PTM@

Range:

N/A

Access:

Read Only

UDC Error Code:

1011

LED:

OK on the DC Power Technology module

Description:

The Power Technology Fault bit is set when the watchdog times out on the D-C Power

Technology module. When this bit is set, the gate firing circuitry will be disabled.

Bit:

12

Hex Value:

1 OOOH

Sug. Var. Name:

FLT_PS@

Range:

N/A

Access:

Read Only

UDC Error Code: 1012
LED:

PWR OK on the Power Supply module

Description:

The PMI Power Supply Fault bit is set when the PMI power supply is not working

correctly.

Bit: 13
Hex Value: 2000H
Sug. Var. Name:

FLT_RW@

Range:

N/A

Access:

Read Only

UDC Error Code:

1013

LED:

N/A

Description:

The PMI Read/Write Failure Fault bit is set when there is a bus fault in the PMI rack. This

is indicated when the Resolver and Drive l/O module and the DC Power Technology module do not
respond to requests from the PMI Processor. This error indicates that there is a hardware problem in

the rack.

Bit: 14
Hex Value: 4000H
Sug. Var. Name:

FLT_RUN@

Range:

N/A

Access:

Read Only

UDC Error Code: 1014
LED:

N/A

Description:

The UDC Run Fault bit is set when the UDC task stops while the minor loop is running

in the PMI Processor.

3-28

Advertising