This means that although the actual data is being updated, the meter port output will change only
when the data changes by 32 or more counts. This level of granularity might be acceptable if the

range of the data were actually 8190 counts, but might not be acceptable if the data range is only

4095 counts. If the programmer had assigned the limits +/-1024, the D/A output step change would

be only 8 counts: 2048/255 = 8.

1 0 0 1

Initiate Change in Setup Register

Hex Value:

N/A

Sug. Var. Name:

N/A

Range:

N/A

Access:

Read/Write

UDC Error Code:

N/A

LED:

N/A

Description:

Set this register equal to a non-zero value to store the new setup register configurations

in UDC memory. You must use this register whether you are changing the meter port setup via an

application task or via l/O Monitor.