C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 102

-

Mode = Operating mode (1 = Winter)

-

SPH1 = LB winter set point

-

PC11 = Regulation type (0 = Lateral band)

-

PC12 = Regulation band

-

PC23 = Heat pump set point lower limit

-

PC24 = Heat pump set point upper limit


6.5.2

Neutral-zone (NZ) regulation

This regulation requires the definition of a neutral zone (NZ) around the set point, within which no
decision will be taken as to the activation or de-activation of compressors in use at the time.
If the outlet temperature is found to be outside the neutral zone, the compressors are activated/de-
activated, in order to bring the temperature value back within the neutral zone.
The requests for switching ON/OFF for the various power steps provided by compressors in
summer operating mode (chiller) will follow this logic:

Switching ON: when the outlet temperature exceeds the neutral zone.

Switching OFF: when the outlet temperature falls below the neutral zone.


-

Mode = Operating mode (0 = Summer)

-

SPC1 = NZ summer set point

-

PC11 = Regulation type (1 = Neutral zone)

-

PC14 = Neutral zone

-

PC17 = Extra time for out-of-zone request

-

PC21 = Chiller set point lower limit

-

PC22 = Chiller set point upper limit


The requests for switching ON/OFF for the various power steps provided by compressors in winter
operating mode (heat pump) will follow this logic:

Switching ON: when the outlet temperature falls below the neutral zone.

Switching OFF: when the outlet temperature exceeds the neutral zone.

SP

Neutral zone

Compressor

start-up

Compressor

shutdown

Outlet T

Steps

Inlet T

SP

SP - PB