C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 78

PG00

It sets the unit type:
1: Air-to-air chiller
2: Air-to-air chiller + heat pump
3: Air-to-water chiller
4: Air-to-water chiller + heat pump
5: Air-to-water chiller
6: Air-to-water chiller + heat pump
7: Air-based motocondensing
8: Air-based motocondensing with inverter
9: Water-based motocondensing
10: Water-based motocondensing with
inverter

3

1

10

CO-W

PG01

Number of circuits

2

1

2

CO-W

PG02

It enables the presence of the expansion.

Yes (1)

No (0)

Yes (1)

CO-W

PG03

It sets the number of compressors per circuit.

2

1

3

CO-W

PG08

It enables operation with heat pump only.

No (0)

No (0)

Yes (1)

CO-W

PG09

It sets the number of pumps.

1

0

2

CO-W

PG11

It enables unique condensing:
0: No (2 fans)
1: Yes (1 fan)

No (0)

No (0)

Yes (1)

CO-W

PG13

It sets the type of free-cooling air circuit:
0: Unique with condensing
1: Separate

0

0

1

CO-W

HARDWARE CONFIGURATION PARAMETERS

HA01

It sets the position of the digital output linked
to notification of the global alarm.

6

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

HA02

It sets the position of the digital output linked
to the anti-frost heating elements of Circuit #
1.

5

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

HA03

It sets the position of the digital output linked
to the anti-frost heating elements of Circuit #
2.

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

HA04

It sets the position of the digital output for the
auxiliary relay dedicated to the Operating
Limit function.

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

HA05

It sets the position of the digital output linked
to the circuit inverter valve. 1

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

HA06

It sets the position of the digital output linked
to the circuit inverter valve. 2

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

HA07

It sets the position of the digital output linked
to the liquid solenoid valve # 1.

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

HA08

It sets the position of the digital output linked
to the liquid solenoid valve # 2.

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

HA09

It sets the position of the digital output linked
to the free-cooling ON/OFF valve.

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

HA19

It sets the position of the digital output linked
to the free-cooling motor-operated valve.

0

0

3 (4)

CO-Hw

Outputs 2 and 3
require the AO
expansion.
(4 if expansion
has been
enabled)

HC01

It sets the position of the digital output for
compressor # 1.

2

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

HC02

It sets the position of the digital output for

3

0

6 (12)

CO-Hw

(12 if expansion