C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 71

start-ups of the same compressor.

PC07

Min. time which must elapse between start-
ups of two different compressors.

10

0

999

Sec.

IS-C

PC08

Min. time which must elapse between
shutdowns of two different compressors.

20

0

999

Sec.

IS-C

PC09

Max. number of start-ups for every hour (only
for adaptive regulation).

8

4

12

IS-C

PC10

Number of compressors per circuit which will
be forced in case of a regulating-probe alarm.

1

0

PG03

IS-C

PC11

It sets the regulation type for compressor
management:
0: Lateral band
1: Neutral zone
2: From digital inputs

1

0

2

IS-R

PC12

Proportional band for lateral-band regulation
of compressors

2.5

1.0

20.0

°C

IS-R

PC14

Zone value for neutral-zone regulation of
compressors

3.0

PC15

PC16

°C

IS-R

PC15

Min. value of compressor neutral zone

1.0

0.1

10.0

°C

IS-R

PC16

Max. value of compressor neutral zone

5.0

0.1

10.0

°C

IS-R

PC17

Enabling/release time for subsequent
compressor step outside the neutral zone

20

0

999

Sec.

IS-R

PC18

Enabling for auto-adaptive control of the
compressors’ neutral zone

No (0)

No (0)

Yes (1)

IS-R

PC21

Min. value of summer set point
(chiller)

5.0

-15.0

SPC1

°C

IS-R

PC22

Max. value of summer set point
(chiller)

20.0

SPC1

35.0

°C

IS-R

PC23

Min. value of winter set point
(heat pump)

30.0

10.0

SPH1

°C

IS-R

PC24

Max. value of winter set point
(heat pump)

44.0

SPH1

70.0

°C

IS-R

PC30

Enabling of power limiting from digital input

No (0)

No (0)

Yes (1)

IS-R

PC31

Power limiting for summer

50

0

100

%

IS-R

PC32

Power limiting for winter

50

0

100

%

IS-R

PC35

Enabling of forced shutdown of compressors

No (0)

No (0)

Yes (1)

IS-R

PC36

Summer forced shutdown set point

3.5

-30.0

23.0

°C

IS-R

PC37

Winter forced shutdown set point

52.0

26.0

75.0

°C

IS-R

PC41

Enabling of pump-down
0 : No
1 : Yes, with timing
2 : Yes, with relative threshold

0

0

2

IS-R

PC42

Compressor shutdown time in pump-down

5

0

240

Sec.

IS-R

PC43

Relative threshold for pump-down disabling

1.5

0.0

5.0

Bar

IS-R

PC45

Enabling of high-temperature pressure-switch
control (chiller)

No (0)

No (0)

Yes (1)

IS-R

PC46

Pressure set point for high-temperature
pressure-switch control

27.0

0.0

45.0

Bar

IS-R

PC47

Pressure differential for high-temperature
pressure-switch control

2.0

0.0

5.0

Bar

IS-R

PC48

External high temperature threshold for
pressure-switch control

12.0

-30.0

23.0

°C

IS-R

PC49

Min. time for maintaining pressure-switch
partialisation

10

0

99

Min.

IS-R

PC50

Enabling of low-temperature pressure-switch
control (heat pump)

No (0)

No (0)

Yes (1)

IS-R

PC51

3.2

0.0

10.0

Bar

IS-R

PC52

Pressure differential for low-temperature
pressure-switch control

2.0

0.0

10.0

Bar

IS-R

PC53

External low temperature threshold for

-5.0

-10.0

5.0

°C

IS-R