C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 73

winter operation (heat pump, inverter)

PF26

Min. value for condenser forcing (inverter)

0.0

0.0

100.0

%

IS-F

PF27

Speed-up time at fan start-up (inverter)

4

0

999

Sec.

IS-F

PF31

Lower limit for condensing linear regulation
(inverter)

30.0

0

PF32

%

IS-F

PF32

Upper limit for condensing linear regulation
(inverter)

100.0

PF31

100.0

%

IS-F

PF33

Enabling of regulation under the minimum
condensing limit (inverter)

Yes (1)

No (0)

Yes (1)

IS-F

PF34

Switch-off differential under the minimum
condensing limit (inverter)

2.0

0.0

5.0

Bar

IS-F

PF36

Enabling of pre-start of condensing fans for
high external temperatures

No (0)

No (0)

Yes (1)

IS-F

PF37

External temperature threshold for pre-start of
condensing fan

30.0

20.0

40.0

°C

IS-F

PF38

Fan pre-start speed

50.0

0

100.0

%

IS-F

PF39

Compressor delay from pre-start of
condensing fan

5

0

999

Sec.

IS-F

PF41

Value x1 of fan linearisation table

25.0

0.0

PF42

%

IS-F

PF42

Value x2 of fan linearisation table

50.0

PF41

PF43

%

IS-F

PF43

Value x3 of fan linearisation table

75.0

PF42

100.0

%

IS-F

PF45

Value y1 of fan linearisation table

25.0

0.0

PF46

%

IS-F

PF46

Value y2 of fan linearisation table

50.0

PF45

PF47

%

IS-F

PF47

Value y3 of fan linearisation table

75.0

PF46

100.0

%

IS-F

DEFROSTING PARAMETERS

Pd01

Pressure set point at defrosting start

6.0

0.0

Pd02

Bar

IS-D

Pd02

Pressure set point at defrosting stop

12.0

Pd01

45.0

Bar

IS-D

Pd03

Waiting interval at defrosting start

1200

60

Pd23

Sec.

IS-D

Pd05

Max. duration of defrosting

300

10

600

Sec.

IS-D

Pd06

Duration of dripping

120

0

600

Sec.

IS-D

Pd07

Min. defrost waiting interval after compressor
re-start

60

0

600

Sec.

IS-D

Pd11

Defrosting management via external contact:
0 = Function disabled
1 = Defrosting start from external contact
2 = Defrosting stop from external contact
3 = Defrosting start and stop from external
contact

0

0

3

IS-D

Pd12

Defrosting contact type:
0 = Front
1 = Level

0

0

1

IS-D

Pd20

Enabling of defrosting cycle compensation

No (0)

No (0)

Yes (1)

IS-D

Pd21

External temperature set point for defrosting
compensation start

5.0

Pd22

70.0

IS-D

Pd22

External temperature set point for defrosting
compensation stop

0.0

-30.0

Pd21

IS-D

Pd23

Max. waiting interval at defrosting stop

3600

Pd03

9600

IS-D

PUMP PARAMETERS

PP01

Pump / recirculating fan operation:
0 = Continuous operation
1 = Operation at thermostat’s request
2 = Cyclical operation

0

0

2

IS-P

PP02

ON time in cyclical operation

120

1

999

Sec.

IS-P

PP03

OFF time in cyclical operation

120

1

999

Sec.

IS-P

PP04

Min. interval which must elapse between
pump start-up and first compressor /
recirculating fan start-up

60

1

999

Sec.

IS-P

PP05

Min. interval which must elapse between
circuit shutdown and pump / recirculating fan
shutdown

60

1

999

Sec.

IS-P