2 alarm table – EVCO c-pro nano CHIL User Manual

Page 135

Advertising
background image

C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 135

7.2

Alarm Table


All alarms managed by the application are listed below. The listing order is the same as the one in
which alarms are listed when active.

Code

Alarm description

Type Consequence

Notes

AL01

Input low temperature

S/A

Notification only or
compressors and pump
OFF

Heat pump only
Settable delay

AL02

Input high temperature

S/A

Notification only or
compressors and pump
OFF

Chiller only
Settable delay

AL03

Primary exchanger efficiency Circuit # 1

Manu

Keeps all circuit
compressors OFF

AL13

Primary exchanger efficiency Circuit # 2

Manu

Keeps all circuit
compressors OFF

Settable delay

AL05

Evaporator flow meter

A/M

Compressors OFF
Pump ON for T-secs.

Settable delay
In manual stop,
pump OFF

AL11

High-pressure pressure switch Circuit # 1

Manu

All circuit compressors
OFF

AL12

High-pressure pressure switch Circuit # 2

Manu

All circuit compressors
OFF

AL21

Low-pressure pressure switch Circuit # 1

A/M

All circuit compressors
and fans OFF

AL22

Low-pressure pressure switch Circuit # 2

A/M

All circuit compressors
and fans OFF

Settable start-up
delay and rpm

AL31

Transducer high pressure Circuit # 1

Manu

All circuit compressors
OFF

AL32

Transducer high pressure Circuit # 2

Manu

All circuit compressors
OFF

AL41

Transducer low pressure Circuit # 1

A/M

All circuit compressors
OFF

AL42

Transducer low pressure Circuit # 2

A/M

All circuit compressors
OFF

Settable start-up
delay and rpm

AL51

Failed start-up for low pressure Circuit # 1

Auto

Keeps all circuit
compressors OFF

AL52

Failed start-up for low pressure Circuit # 2

Auto

Keeps all circuit
compressors OFF

AL81

Evaporator anti-frost Circuit # 1

Manu

Circuit compressors
OFF and
Pump ON for T-secs.

AL82

Evaporator anti-frost Circuit # 2

Manu

Circuit compressors
OFF and
Pump ON for T-secs.

AC21

Thermal switch compressor # 1

A/M

Compressor # 1 OFF

AC22

Thermal switch compressor # 2

A/M

Compressor # 2 OFF

AC23

Thermal switch compressor # 3

A/M

Compressor # 3 OFF

AC24

Thermal switch compressor # 4

A/M

Compressor # 4 OFF

AC25

Thermal switch compressor # 5

A/M

Compressor # 5 OFF

AC26

Thermal switch compressor # 6

A/M

Compressor # 6 OFF

Settable delay

AP21

Thermal switch pump # 1

A/M

Pump # 1 OFF (*¹)

AP22

Thermal switch pump # 2

A/M

Pump # 2 OFF (*¹)

AF21

Thermal switch fan Circuit # 1

A/M

Fan # 1 OFF

AF22

Thermal switch fan Circuit # 2

A/M

Fan # 2 OFF

Settable delay

AC01

Operating hours compressor # 1

Auto

Display only

AC02

Operating hours compressor # 2

Auto

Display only

AC03

Operating hours compressor # 3

Auto

Display only

AC04

Operating hours compressor # 4

Auto

Display only

Advertising