EVCO c-pro nano CHIL User Manual
Page 139
![background image](/manuals/675457/139/background.png)
C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 139
Cooling
(Chiller),
1=Winter
Heating (Heat
pump)
1284 SetpointEstivo_Attuale
8.5
-15.0
23.0
R/W
1285 SetpointInverno_Attuale
44.0
23.0
70.0
R/W
1286 Abilitazione_FC
0
0
1
R/W
1287 abiReg_FC_ValvolaOnOff
0
0
1
R/W
1288 Setpoint_FreeCooling_Attuale
0.0
-15.0
23.0
R/W
1289 StatoSbrinamento_C1
0
0
8
0=OFF.
1..3=WAIT
4..6=Defrosting
7..8=Dripping
R/W
1290 StatoSbrinamento_C2
0
0
8
0=OFF.
1..3=WAIT
4..6=Defrosting
7..8=Dripping
R/W
1291 PowerRequested
0
0
100
[%]
R/W
1292 PowerSupplied
0
0
100
[%]
R/W
1293 StatoCompressori[0]
0
0
6
R/W
1294 StatoCompressori[1]
0
0
6
R/W
1295 StatoCompressori[2]
0
0
6
R/W
1296 StatoCompressori[3]
0
0
6
R/W
1297 StatoCompressori[4]
0
0
6
R/W
1298 StatoCompressori[5]
0
0
6
R/W
1299 StatoFan1
0
0
6
0=Disabled,
1=OFF, 2=Wait
ON, 3=ON,
4=Wait OFF,
5=ALL,
6=Manual
R/W
1300 StatoFan2
0
0
6
0=Disabled,
1=OFF, 2=Wait
ON, 3=ON,
4=Wait OFF,
5=ALL,
6=Manual
R/W
1301 StatoPompa1_Ventilatore
0
0
3
0=Disabled,
1=OFF, 2=ON,
3=Alarm
R/W
1302
0
0
3
0=Disabled,
1=OFF, 2=ON,
3=Alarm
R/W
1537 MOdE_ModoFunzionamento
0
0
1
0=Cool
(Chiller),
R/W