EVCO c-pro nano CHIL User Manual
Page 70
![background image](/manuals/675457/70/background.png)
C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 70
PM13
PM14
PM15
PM16
0: Auto – normal operation
1: Manu – manual operation
One for each compressor.
PM21
PM22
PM23
PM24
PM25
PM26
During manual operation, it forces the start-
up/shutdown of the compressor. 0: switches
the compressor OFF
1: switches the compressor ON
One for each compressor.
0
0
1
MA-M
PM51
It enables the manual/automatic operation of
the condensing fan in Circuit # 1.
0: Auto – normal operation
1: Manu – manual operation
0
0
1
MA-M
PM52
It enables the manual/automatic operation of
the condensing fan in Circuit # 2.
0: Auto – normal operation
1: Manu – manual operation
0
0
1
MA-M
PM61
During manual operation, it forces the value of
the condensing fan in Circuit # 1.
0.0
0.0
100.0
%
MA-M
PM62
During manual operation, it forces the value of
the condensing fan in Circuit # 2.
0.0
0.0
100.0
%
MA-M
PM71
It enables the manual/automatic operation of
the free-cooling fan.
0: Auto – normal operation
1: Manu – manual operation
0.0
0.0
100.0
%
MA-M
PM72
During manual operation, it forces the value of
the free-cooling fan.
0.0
0.0
100.0
%
MA-M
PM81
Calibration of the input (ambient) temperature
probe
0.0
-20.0
20.0
°C
MA-CA
PM82
Calibration of outlet (delivery) temperature
probe # 1
0.0
-20.0
20.0
°C
MA-CA
PM83
Calibration of condensing probe in Circuit # 1
0.0
-20.0
20.0
Bar
MA-CA
PM84
Calibration of the AI04 probe
0.0
-20.0
20.0
Bar/°C
MA-CA
PM85
Calibration of the AI05 probe
0.0
-20.0
20.0
°C
MA-CA
PM86
Calibration of outlet (delivery) temperature
probe # 2
0.0
-20.0
20.0
°C
MA-CA
PM87
Calibration of AI07 pressure probe
0.0
-20.0
20.0
Bar
MA-CA
PM88
Calibration of AI08 pressure probe
0.0
-20.0
20.0
Bar
MA-CA
PSd2
It modifies the password at Maintenance
Operator level.
0
-999
9999
MA-F
INSTALLATION OPERATOR PARAMETERS
COMPRESSOR PARAMETERS
PC01
Rotation type used for compressor
management:
0: FIFO
1: LIFO
2: FIFO + hours
3: LIFO + hours
0
0
3
IS-C
PC02
Enabling mode of compressors in the two
circuits:
0: Circuit balancing
1: Circuit saturation
0
0
1
IS-C
Only on twin
circuits
PC04
Min. time for which the compressor must
remain ON, even if a shutdown has been
requested.
20
0
999
Sec.
IS-C
PC05
Min. time for which the compressor must
remain OFF, even if a start-up has been
requested.
120
0
999
Sec.
IS-C
PC06
Min. time which must elapse between two
360
0
999
Sec.
IS-C