C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 80

the second step of compressor regulation. (In
motocondensing units, compressor activation
is via DI.)

has been
enabled)

Hd13

It sets the position of the digital input linked to
the third step of compressor regulation. (In
motocondensing units, compressor activation
is via DI.)

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

Hd14

It sets the position of the digital input linked to
the fourth step of compressor regulation. (In
motocondensing units, compressor activation
is via DI.)

0

0

6(12)

CO-Hw

(12 if expansion
has been
enabled)

Hd15

It sets the position of the digital input linked to
the fifth step of compressor regulation. (In
motocondensing units, compressor activation
is via DI.)

0

0

6(12)

CO-Hw

(12 if expansion
has been
enabled)

Hd16

It sets the position of the digital input linked to
the sixth step of compressor regulation. (In
motocondensing units, compressor activation
is via DI.)

0

0

6(12)

CO-Hw

(12 if expansion
has been
enabled)

Hd20

It sets the position of the digital input linked to
the low-pressure alarm on the pressure switch
of Circuit # 1.

6

0

6(12)

CO-Hw

(12 if expansion
has been
enabled)

Hd21

It sets the position of the digital input linked to
the high-pressure alarm on the pressure switch
of Circuit # 1.

1

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

Hd22

It sets the position of the digital input linked to
the low-pressure alarm on the pressure switch
of Circuit # 2.

6

0

6(12)

CO-Hw

(12 if expansion
has been
enabled)

Hd23

It sets the position of the digital input linked to
the high-pressure alarm on the pressure switch
of Circuit # 2.

1

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

Hd41

It sets the position of the digital input linked to
the thermal alarm of compressor # 1.

2

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

Hd42

It sets the position of the digital input linked to
the thermal alarm of compressor # 2.

3

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

Hd43

It sets the position of the digital input linked to
the thermal alarm of compressor # 3.

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

Hd44

It sets the position of the digital input linked to
the thermal alarm of compressor # 4.

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

Hd45

It sets the position of the digital input linked to
the thermal alarm of compressor # 5.

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

Hd46

It sets the position of the digital input linked to
the thermal alarm of compressor # 6.

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

Hd81

It sets the position of the digital inputs linked
to the thermal alarm of fan # 1.

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

Hd82

It sets the position of the digital inputs linked
to the thermal alarm of fan # 2.

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

Hd91

It sets the position of the digital inputs linked
to the thermal alarm of pump # 1.

5

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)

Hd92

It sets the position of the digital inputs linked
to the thermal alarm of pump # 2.

0

0

6 (12)

CO-Hw

(12 if expansion
has been
enabled)