C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 92

6.2.8

Twin-circuit water-to-water units

PG01 = 2
Twin-circuit

PG00 = 5
Water-to-water chiller

PG00 = 6
Water-to-water chiller + heat pump

Analogue inputs

AI 1

(NTC)

Inlet water temperature

Inlet water temperature

AI 2

(NTC)

Outlet water temperature Circuit # 1

Outlet water temperature Circuit # 1

AI 3

(NTC / 4..20 mA)

Condensing pressure/temperature Circuit #
1

Condensing pressure/temperature Circuit #
1

AI 4

(NTC / 4.20 mA / DI)

Used as DI6

Used as DI6

AI 5

(NTC)

Geothermal heat exchanger temperature

Geothermal heat exchanger temperature

AI 6

(NTC)

Outlet water temperature Circuit # 2

Outlet water temperature Circuit # 2

AI 7

(4..20 mA)

Condensing pressure/temp. Circuit # 2

Condensing pressure/temp. Circuit # 2

AI 8

(4..20 mA / DI)

Used as DI12

Used as DI12

Digital inputs

DI 1

High-pressure pressure switch Circuit # 1

High-pressure pressure switch Circuit # 1

DI 2

Thermal overload switch compressor # 1

Thermal overload switch compressor # 1

DI 3

Thermal overload switch compressor # 2

Thermal overload switch compressor # 2

DI 4

Flow meter

Flow meter

DI 5

Thermal overload switch pump # 1

Thermal overload switch pump # 1

DI 6 ()

Low-pressure pressure switch Circuit # 1

Low-pressure pressure switch Circuit # 1

DI 7

High-pressure pressure switch Circuit # 2

High-pressure pressure switch Circuit # 2

DI 8

Thermal overload switch compressor # 3

Thermal overload switch compressor # 3

DI 9

Thermal overload switch compressor # 4

Thermal overload switch compressor # 4

DI 10

Secondary set point

Secondary set point

DI 11

-

Summer/winter commutation

DI 12 ()

Low-pressure pressure switch Circuit # 2

Low-pressure pressure switch Circuit # 2

Digital outputs

DO 1

Circulating pump # 1

Circulating pump # 1

DO 2

Compressor # 1

Compressor # 1

DO 3

Compressor # 2

Compressor # 2

DO 4

Anti-frost heating coil # 1

Inverter valve Circuit # 1

DO 5

Fluid solenoid valve Circuit # 1

Fluid solenoid valve Circuit # 1

DO 6

General alarm

General alarm

DO 7

Geothermal by-pass solenoid valve

Geothermal by-pass solenoid valve

DO 8

Compressor # 3

Compressor # 3

DO 9

Compressor # 4

Compressor # 4

DO 10

Anti-frost heating coil # 2

Inverter valve Circuit # 2

DO 11

Fluid solenoid valve Circuit # 2

Fluid solenoid valve Circuit # 2

DO 12

-

-

Analogue outputs

AO 1

(PWM)

-

-

AO 2

(0..10 V / 4..20 mA)

Condensing valve # 1 control

Condensing valve # 1 control

AO 3

(0..10 V / 4..20 mA)

Condensing valve # 2 control

Condensing valve # 2 control

AO 4

(PWM)

-

-