EVCO c-pro nano CHIL User Manual
Page 147
![background image](/manuals/675457/147/background.png)
C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 147
1768 PH13_Modbus_Parity
2
0
2
0=None,
1=Odd, 2=Even
R/W
1769 PH14_Modbus_StopBit
0
0
1
0=1 bit, 1=2
bits
R/W
1770 PH15_RipristinoDefaultParametri
0
0
1
R/W
1771 PH16_Logic_DO_ReverseValve
0
0
1
R/W
1772 PH17_Logic_DI_Alarm
1
0
1
R/W
1773 PH18_Logic_DO_Alarm
0
0
1
R/W
1774 PH19_Logic_DI_Mode
0
0
1
R/W
1775 PH20_Logic_DI_Flow
1
0
1
R/W
1776 PH21_AbilitaSondaTIngresso
1
0
1
R/W
1777 PH22_AbilitaSondaTUscita_C1
1
0
1
R/W
1778 PH23_AbilitaSondaTUscita_C2
1
0
1
R/W
1779 PH24_AbilitaSondaEsterna
1
0
1
0=Disabled
R/W
1780 PH25_En_OffsetSetPoint_ByDig
0
0
1
R/W
1781 PH26_En_OffsetSetPoint_BySup
0
0
1
R/W
1782 PH27_AbilitaSetPointDinamico
0
0
1
R/W
1783 PH29_Logic_DI_StepsCompressori
0
0
1
R/W
1784 PH31_RefrigerationType
3
0
6
0=none,
1=R22,
2=R134a,
3=R404A,
4=R407C,
5=R410A,
6=R507
R/W
1785 PH32_Temp_UM
0
0
1
0=°C, 1=°F
R/W
1786 PH33_Press_UM
0
0
1
0=bar, 1=psi
R/W
1787 PH43_Tipo_AI3
4
2
4
2=NTC, 3=Not
used, 4=4..20
mA
R/W
1788 PH44_Tipo_AI4
1
0
4
0=Disabled
probe, 1=DI06,
2=External
temp.,
3=Accumulatio
n temp.,
4=Evaporation
C1
R/W
1789 PH45_Tipo_AI8
1
0
2
0=Disabled;
1=DI06,
2=Evaporation
C2
R/W
1790
PH48_TrasduttoreUnico_Separato_SbrinamentoCondensazi
one
0
0
1
0=Single,
1=Separate
R/W