EVCO c-pro nano CHIL User Manual

Page 145

Advertising
background image

C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 145

1701 PP07_SpegnimentoPompaInSbrinamento

0

0

1

R/W

1702 PP08_DeltaOreRotazione

4

1

240

R/W

1703 PP09_TempoFunzPompeConBassoQuantitativoAcqua

15

0

999

R/W

1704 PP10_TempoFunzPompeConBassaTemperatura

15

0

999

R/W

1705 PP11_Abilita_HotStart

0

0

1

R/W

1706 PP12_SetPoint_HotStart

36.0

0.0

70.0

R/W

1707

PP13_Diff_HotStart

4.0

0.1

10.0

R/W

1708 Pr01_AbilitaResistenzeAntigelo

1

0

1

R/W

1709 Pr02_SetpointResAntigelo

5.0

-30.0

10.0

R/W

1710 Pr03_DifferenzialeResAntigelo

2.0

0.1

10.0

R/W

1711 Pr04_ForzaResistenzeInErroreSonda

0

0

1

R/W

1712 Pr11_SetpointAllarmeAntigelo

3.0

-30.0

10.0

R/W

1713 Pr12_DifferenzialeAllarmeAntigelo

2.0

0.1

10.0

R/W

1714 PS01_AbilitaFree_Cooling

0

0

1

R/W

1715 PS02_BandaModulazione_SerrandaFC

3.0

0.1

20.0

R/W

1716 PS03_MinimaVelocita_FC

0.00

0.00

100.00

R/W

1717 PS04_MassimaVelocita_FC

100.0

0

0.00

100.00

R/W

1718 PS11_SetDifferenziale_FC

3.0

2.0

9.9

R/W

1719 PS13_Diff_FC

2.0

0.5

5.0

R/W

1720 PS14_TempoMinimoAbilitazione_FC

30

0

240

R/W

1721 PS15_IsteresiValvolaOnOff_FC

0.5

0.1

5.0

R/W

1722 PS16_SogliaMassimaAperturaValvola_FC

2.0

0.1

20.0

R/W

1723 PS21_AbilitaFree_Cooling_ConCompressori

1

0

1

R/W

1724 PA01_FlowStartup_AlarmDelay

10

1

999

R/W

1725 PA02_FlowRunning_AlarmDelay

1

1

999

R/W

1726 PA03_NumeroInterventiAllarmeFlusso

3

0

9

R/W

1727 PA04_RitardoErroreSonda

10

0

240

R/W

1728 PA05_SetpointAllarmeAltaTemp

30.0

10.0

40.0

R/W

1729 PA06_SetpointAllarmeBassaTemp

15.0

10.0

40.0

R/W

1730 PA07_RitardoAttivazioneAllarmeTemperatura

30

1

999

R/W

1731 PA08_SegnalazioneAllarmeTemperatura

0

0

1

R/W

1732 PA09_DifferenzialeAllarmeTemp

0.5

0.1

10.0

R/W

1733

15

0

999

R/W

1734 PA11_SetAllarmeBassaPressione

3.0

0.1

145.0

bar/psi

R/W

Advertising