C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 79
compressor # 2.
has been
enabled)
HC03
It sets the position of the digital output for
compressor # 3.
0
0
6 (12)
CO-Hw
(12 if expansion
has been
enabled)
HC04
It sets the position of the digital output for
compressor # 4.
0
0
6 (12)
CO-Hw
(12 if expansion
has been
enabled)
HC05
It sets the position of the digital output for
compressor # 5.
0
0
6 (12)
CO-Hw
(12 if expansion
has been
enabled)
HC06
It sets the position of the digital output for
compressor # 6.
0
0
6 (12)
CO-Hw
(12 if expansion
has been
enabled)
HF31
It sets the position of the analogue output of
the condensing fan in Circuit # 1.
1
0
3 (4)
CO-Hw
Outputs 2 and 3
require the AO
expansion.
(4 if expansion
has been
enabled)
HF32
It sets the position of the analogue output of
the condensing fan in Circuit # 2.
0
0
3 (4)
CO-Hw
Outputs 2 and 3
require the AO
expansion.
(4 if expansion
has been
enabled)
HF34
It sets the position of the analogue output
linked to the free-cooling fan output (in case it
is separated from the condensing fan).
0
0
3 (4)
CO-Hw
Outputs 2 and 3
require the AO
expansion.
(4 if expansion
has been
enabled)
HP01
It sets the position of the digital output for
pump # 1 / recirculating fan.
1
0
6 (12)
CO-Hw
(12 if expansion
has been
enabled)
HP02
It sets the position of the digital output for
pump # 2.
0
0
6 (12)
CO-Hw
(12 if expansion
has been
enabled)
Hd01
It sets the position of the digital input for the
global ON/OFF.
0
0
6 (12)
CO-Hw
(12 if expansion
has been
enabled)
Hd02
It sets the position of the digital input linked to
the secondary set point for compressor
management.
0
0
6 (12)
CO-Hw
(12 if expansion
has been
enabled)
Hd05
It sets the position of the digital input linked to
the summer/winter operating mode.
0
0
6 (12)
CO-Hw
(12 if expansion
has been
enabled)
Hd06
It sets the position of the digital input linked to
flow detection.
4
0
6 (12)
CO-Hw
(12 if expansion
has been
enabled)
Hd07
It sets the position of the digital input linked to
the power-limiting command.
0
0
6 (12)
CO-Hw
(12 if expansion
has been
enabled)
Hd09
It sets the position of the digital input linked to
the defrosting command from external contact.
0
0
6 (12)
CO-Hw
(12 if expansion
has been
enabled)
Hd11
It sets the position of the digital input linked to
the first step of compressor regulation. (In
motocondensing units, compressor activation
is via DI.)
0
0
6 (12)
CO-Hw
(12 if expansion
has been
enabled)
Hd12
It sets the position of the digital input linked to
0
0
6 (12)
CO-Hw
(12 if expansion