C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 75
PA16
Enabling of low-pressure control at start-up
and at low temperatures
Yes (1)
No (0)
Yes (1)
IS-S
PA17
Low-pressure alarm threshold at start-up and
at low temperatures
1.0
0.1
9.9
Bar
IS-S
PA18
Low-pressure alarm reset differential at start-
up and at low temperatures
0.5
0.1
4.0
Bar
IS-S
PA19
Control duration at triggering of low-pressure
alarm at low temperatures
120
10
PA13
Sec.
IS-S
PA20
Min. duration of alarm delay for triggering of
low-pressure alarm at compressor start-up
240
0
999
Sec.
IS-S
PA21
High-pressure alarm threshold
28.0
0.0
45.0
Bar
IS-S
PA22
High-pressure alarm reset differential
5.0
0.1
30.0
Bar
IS-S
PA25
Enabling of primary exchanger efficiency
alarm
No (0)
No (0)
Yes (1)
IS-S
PA26
Min. difference threshold for primary
exchanger
2.0
0.1
20.0
°C
IS-S
PA27
By-pass time for primary exchanger efficiency
alarm
120
0
999
Sec.
IS-S
PA40
It enables the alarm connected with operating
hours of compressors
Yes (1)
No (0)
Yes (1)
IS-S
PA41
It sets the triggering delay connected with the
compressor thermal alarm
10
0
999
Sec.
IS-S
PA42
It sets the type of reset for the compressor
thermal alarm
0: A - Automatic
1: M – Manual
M
A (0)
M (1)
IS-S
PA60
It enables the alarm connected with operating
hours of pumps
Yes (1)
No (0)
Yes (1)
IS-S
PA62
It sets the type of reset for the pumps /
delivery fan thermal alarm
0: A - Automatic
1: M – Manual
M
A (0)
M (1)
IS-S
PA80
It enables the alarm connected with operating
hours of condensing fans
Yes (1)
No (0)
Yes (1)
IS-S
PA81
It sets the triggering delay connected with the
condensing fan thermal alarm
10
0
999
Sec.
IS-S
PA82
It sets the type of reset for the condensing fan
thermal alarm
0: A - Automatic
1: M – Manual
M
A (0)
M (1)
IS-S
PA99
Notification delay interval for expansion
alarm
5
0
999
Sec.
IS-S
OTHER PARAMETERS
PH01
It sets the minimum full-scale value for the
condensing probe.
0.0
-10.0
PH02
Bar
IS-V
PH02
It sets the maximum full-scale value for the
condensing probe.
30.0
PH01
45.0
Bar
IS-V
PH04
It sets the probe for the change of
summer/winter operating mode: automatic
change-over
0: External air temperature
1: Ambient air temperature
0
0
1
IS-V
PH05
It enables the start-up/shutdown of the
machine by pressing the ESC/Stand-By key.
Yes (1)
No (0)
Yes (1)
IS-V
PH06
It enables the change of summer/winter
operating mode: automatic change-over.
No (0)
No (0)
Yes (1)
IS-V
PH07
It enables the start-up/shutdown of the
machine from a digital input.
No (0)
No (0)
Yes (1)
IS-V
PH08
It enables the change of summer/winter
operating mode from digital input.
No (0)
No (0)
Yes (1)
IS-V