C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 75

PA16

Enabling of low-pressure control at start-up
and at low temperatures

Yes (1)

No (0)

Yes (1)

IS-S

PA17

Low-pressure alarm threshold at start-up and
at low temperatures

1.0

0.1

9.9

Bar

IS-S

PA18

Low-pressure alarm reset differential at start-
up and at low temperatures

0.5

0.1

4.0

Bar

IS-S

PA19

Control duration at triggering of low-pressure
alarm at low temperatures

120

10

PA13

Sec.

IS-S

PA20

Min. duration of alarm delay for triggering of
low-pressure alarm at compressor start-up

240

0

999

Sec.

IS-S

PA21

High-pressure alarm threshold

28.0

0.0

45.0

Bar

IS-S

PA22

High-pressure alarm reset differential

5.0

0.1

30.0

Bar

IS-S

PA25

Enabling of primary exchanger efficiency
alarm

No (0)

No (0)

Yes (1)

IS-S

PA26

Min. difference threshold for primary
exchanger

2.0

0.1

20.0

°C

IS-S

PA27

By-pass time for primary exchanger efficiency
alarm

120

0

999

Sec.

IS-S

PA40

It enables the alarm connected with operating
hours of compressors

Yes (1)

No (0)

Yes (1)

IS-S

PA41

It sets the triggering delay connected with the
compressor thermal alarm

10

0

999

Sec.

IS-S

PA42

It sets the type of reset for the compressor
thermal alarm
0: A - Automatic
1: M – Manual

M

A (0)

M (1)

IS-S

PA60

It enables the alarm connected with operating
hours of pumps

Yes (1)

No (0)

Yes (1)

IS-S

PA62

It sets the type of reset for the pumps /
delivery fan thermal alarm
0: A - Automatic
1: M – Manual

M

A (0)

M (1)

IS-S

PA80

It enables the alarm connected with operating
hours of condensing fans

Yes (1)

No (0)

Yes (1)

IS-S

PA81

It sets the triggering delay connected with the
condensing fan thermal alarm

10

0

999

Sec.

IS-S

PA82

It sets the type of reset for the condensing fan
thermal alarm
0: A - Automatic
1: M – Manual

M

A (0)

M (1)

IS-S

PA99

Notification delay interval for expansion
alarm

5

0

999

Sec.

IS-S

OTHER PARAMETERS

PH01

It sets the minimum full-scale value for the
condensing probe.

0.0

-10.0

PH02

Bar

IS-V

PH02

It sets the maximum full-scale value for the
condensing probe.

30.0

PH01

45.0

Bar

IS-V

PH04

It sets the probe for the change of
summer/winter operating mode: automatic
change-over
0: External air temperature
1: Ambient air temperature

0

0

1

IS-V

PH05

It enables the start-up/shutdown of the
machine by pressing the ESC/Stand-By key.

Yes (1)

No (0)

Yes (1)

IS-V

PH06

It enables the change of summer/winter
operating mode: automatic change-over.

No (0)

No (0)

Yes (1)

IS-V

PH07

It enables the start-up/shutdown of the
machine from a digital input.

No (0)

No (0)

Yes (1)

IS-V

PH08

It enables the change of summer/winter
operating mode from digital input.

No (0)

No (0)

Yes (1)

IS-V