3 alarm relay – EVCO c-pro nano CHIL User Manual

Page 136

Advertising
background image

C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 136

AC05

Operating hours compressor # 5

Auto

Display only

AC06

Operating hours compressor # 6

Auto

Display only

AP01

Operating hours pump # 1

Auto

Display only

AP02

Operating hours pump # 2

Auto

Display only

AF01

Operating hours fan Circuit # 1

Auto

Display only

AF02

Operating hours fan Circuit # 2

Auto

Display only

ES01

Inlet temperature probe faulty or not
connected

Auto

Settable number of ON
compressors

ES02

C1 outlet temperature probe faulty or not
connected

Auto

Settable number of ON
compressors (*²)

ES03

Condensing pressure transducer C1 faulty or
not connected

Auto

Settable fan forcing

ES04

AI04 probe faulty or not connected

Auto

Inhibits functions
using it

ES05

AI05 probe faulty or not connected

Auto

Inhibits functions
using it

ES06

C2 outlet temperature probe faulty or not
connected

Auto

Settable number of ON
compressors (*²)

ES07

Evaporating pressure transducer C2 faulty
or not connected

Auto

Settable fan forcing

ES08

AI08 probe faulty or not connected

Auto

Inhibits functions
using it

Settable delay

EN01

Expansion communication alarm

Auto

Display only

Settable delay


Note: (*¹) If this is the only pump, it switches OFF all compressors and fans; otherwise, it switches ON the other
pump.

(*²) If Pr03=1, the output probe fault alarm on that circuit switches ON the associated anti-frost heating coils.
S/A = Notification - only or auto-reset alarm (settable via parameter).
A/M = Auto or manual-reset alarm (settable via parameter or by number of events/hour).


7.3

Alarm Relay


The program offers the possibility of managing a cumulative alarm relay. Enabling of this output
depends on whether or not the associated parameter Alarm DO position HA01 has been set. To
enable it, it is sufficient to set such value as different from zero; if a zero value is kept, the alarm
relay will not be used.
Via parameter Alarm DO logic-{}- PH18, it is possible to establish the polarity (NO or NC) of the
alarm output.