EVCO c-pro nano CHIL User Manual

Page 133

Advertising
background image

C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 133

6.17.12Resetting of default parameters

Using the “Parameter resetting” procedure, all system parameters can be reset to their original
default values. After entering the InSt->MAP menu – which is only accessible while the machine is
switched OFF – set parameter PH15=1 and wait for the “0” value to reappear on the display; the
system will automatically reset all parameters back to their default values.
After this operation, it is necessary to power down the machine and then power it up again, to avoid
the risk of malfunctions.


6.17.13Programming key

The values of all system parameters can be saved on the programming key, to be subsequently
copied to one or more compatible devices. The saving or resetting operation can only be carried out
while the machine is switched OFF, by connecting the programming key to the programming
connector.


To save a given parameter map onto the programming key:

-

Enter the InSt->MAP menu and select the “Stor” item, using the UP or
DOWN key;

-

Press the SET (ENTER) key: parameter transfer to the programming
key is highlighted by flashing of the associated LED;

-

Wait for LED flashing to stop: if it is GREEN now, the operation was
successful, otherwise the LED is RED.

To copy a given parameter map from the programming key to a device:

-

Enter the InSt->MAP menu and select the “rESt” item, using the UP or
DOWN key;

-

Press the SET (ENTER) key: parameter transfer from the programming
key to the device is highlighted by flashing of the associated LED;

-

Wait for LED flashing to stop: if it is GREEN now, the operation was
successful, otherwise the LED is RED.

Note: Information relating to the product and product version is stored onto the programming key,
thus allowing the transfer of parameter maps only between devices which are compatible with one
another.

Advertising