C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 106

pressure value is stored, the fluid solenoid valve is disabled, and, once the evaporation pressure
value has fallen by the Pump-down pressure differential PC43, the compressor is switched OFF.


Anyway, there is always the Compressor switch-OFF delay in pump-down, should the switch-OFF
pressure threshold not be reached, or should evaporation probes be faulty.

In order to enable this function, the following parameters must be set:

-

PC41 = 2: Function enable

-

PC42: Pump-down time

-

PC43: Pump-down differential

-

HA07: Position of solenoid valve digital output, Circuit # 1

-

HA08: Position of solenoid valve digital output, Circuit # 2

-

PH44 = 4: Enabling of evaporation probe, Circuit # 1

-

PH45 = 2: Enabling of evaporation probe, Circuit # 2


Note: In case of alarm, the system must ignore the compressor shutdown delay.

6.6.5

Protection timings

There now follows a list of all timings connected with the management of compressors.

Protection timings

The purpose of these timings is that of protecting mechanical units from the various start-up stresses
to which they are subjected.

Last
compressor
request

Evap. P

Solenoid
valve

Compressor

PC43
Pump-down
pressure
differential

PC42 Pump-down disable delay

t

t

t

t