4 single-circuit motocondensing air-based units – EVCO c-pro nano CHIL User Manual

Page 86

Advertising
background image

C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 86

6.2.4

Single-circuit motocondensing air-based units

PG01 = 1
Single-circuit

PG00 = 7
Motocondensing, air-based

PG00 = 8
Motocondensing, air-based, with cycle
inversion

Analogue inputs

AI 1

(NTC)

-

-

AI 2

(NTC)

-

-

AI 3

(NTC / 4..20 mA)

Condensing pressure

Condensing pressure

AI 4

(NTC / 4.20 mA / DI)

Used as DI 6

Used as DI 6

Digital inputs

DI 1

Fan thermal switch

Fan thermal switch

DI 2

Thermal switch compressor # 1

Thermal switch compressor # 1

DI 3

Thermal switch compressor # 2

Thermal switch compressor # 2

DI 4

Compressor 1

st

step control

Compressor 1

st

step control

DI 5

Compressor 2

nd

step control

Compressor 2

nd

step control

DI 6 (*)

Low-pressure pressure switch

Low-pressure pressure switch

Digital outputs

DO 1

-

-

DO 2

Compressor # 1

Compressor # 1

DO 3

Compressor # 2

Compressor # 2

DO 4

-

Circuit inverter valve

DO 5

-

-

DO 6

General alarm

General alarm

Analogue outputs

AO 1

(PWM)

Condensing fan

Condensing fan

AO 2

(0..10 V / 4..20 mA)

-

-

AO 3

(0..10 V / 4..20 mA)

-

-

By selecting these units, default values for parameters PC11=2 and PH44=1 are automatically set,
while a “0” value is set for all input/output position parameters not specified in this configuration.

(*) Digital input derived from analogue input (parameter PH44).