15 temperature alarm control – EVCO c-pro nano CHIL User Manual

Page 122

Advertising
background image

C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 122

6.15

Temperature Alarm Control

6.15.1

Low and high temperature alarm management

According to operating mode, a check is carried out on the exchanger inlet temperature, triggering
an alarm where appropriate.

-

In winter operation (heat pump), if the temperature falls below a given threshold for a
settable lapse of time, a “low temperature” alarm is generated: AL01.

-

In summer operation (chiller), if the inlet temperature exceeds a given threshold for a
settable lapse of time, a “high temperature” alarm is generated: AL02

Via a configuration parameter, alarms can be set to be display-only alarms, or to stop the machine.
It is also possible to set a temperature-alarm inhibition delay from system start-up, so as to give the
machine a chance to reach full power.

-

PA05 = High-temperature alarm set point

-

PA06 = Low-temperature alarm set point

-

PA07 = Temperature alarm enable delay

-

PA08 = Temperature alarm management mode (display-only / machine stop)

-

PA09 = Temperature alarm differential

-

PA10 = System start-up alarm inhibition time


These alarms are only detected when the machine is switched ON.

6.15.2

Management of primary exchanger efficiency alarm

If this alarm AL03 (and AL13 for Circuit # 2) is enabled (PA25 = 1), a check is made as to whether
the difference between input and outlet temperatures, situated on the primary exchanger, is below a
Primary exchanger difference minimum threshold PA26 for a By-pass time for primary exchanger
efficiency alarm PA27
.
This alarm is not managed during defrosting, if probes are in alarm status and this alarm is a
manual-reset alarm.
This alarm is only detected when the machine is switched ON.

Advertising
This manual is related to the following products: