EVCO c-pro nano CHIL User Manual
Page 77
![background image](/manuals/675457/77/background.png)
C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 77
0: ° Celsius
1: ° Fahrenheit
PH33
It sets the pressure measurement unit:
0: Bar
1: psi
0 (Bar)
0
1
IS-V
PH43
It sets the type of universal analogue input AI3
for the condensing probe.
2: NTC
3: 0-20 mA
4: 4-20 mA
4
2
4
IS-V
PH44
It sets the type of universal analogue input
AI4.
0: Probe disabled
1: used as DI06
2: NTC external temperature
3: NTC accumulation temperature
4: Pressure 4-20 mA (Evaporation C1)
1
DI06
0
4
IS-V
PH45
It sets the type of analogue input AI8.
0: Probe disabled
1: used as DI12
2: Pressure 4-20 mA (Evaporation C2)
1
DI12
0
2
IS-V
PH48
It sets the single or separate transducer to
summer condensing and winter defrosting.
0: Single (condensing probes)
1: Separate (condensing probes / evaporation
probes)
0
0
1
IS-V
PH50
It sets displaying with icons only.
0 : No
1: Yes
No (0)
No (0)
Yes (1)
IS-V
PH51
It sets the display of numeric icons.
0 : No
1: Yes
Yes (1)
No (0)
Yes (1)
IS-V
PH52
It sets the display of EVCO icon.
0 : No
1: Yes
Yes (1)
No (0)
Yes (1)
IS-V
PH53
It sets the meaning of the Summer and Winter
icons.
0: Summer = Cooling (chiller mode)
Winter = Heating (heat pump mode)
1: Summer = Heating (heat pump mode)
Winter = Cooling (chiller mode)
0
0
1
IS-V
PH61
It sets the logic of the digital input used for
remote ON/OFF control.
0: NO – Normally open
1: NC – Normally closed
NO
NO (0)
NC (1)
IS-V
PH62
It sets the logic of the digital input used for the
secondary set.
0: NO – Normally open
1: NC – Normally closed
NO
NO (0)
NC (1)
IS-V
PH63
It sets the logic of the digital input used for
power limiting.
0: NO – Normally open
1: NC – Normally closed
NO
NO (0)
NC (1)
IS-V
PH64
It sets the logic of the digital input used for
remote defrosting.
0: NO – Normally open
1: NC – Normally closed
NO
NO (0)
NC (1)
IS-V
PSd3
It sets the Installation Operator level
password.
0
-999
9999
IS-V
CONSTRUCTOR PARAMETERS