C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 72
pressure-switch control
PC54
Outlet water high-temperature threshold for
pressure-switch control
48.0
30.0
70.0
°C
IS-R
PC61
Summer commutation set point
20.0
PC62
70.0
°C
IS-R
PC62
Winter commutation set point
10.0
0.0
PC61
°C
IS-R
PC64
Max. dynamic offset compared to summer set
point (chiller)
-10.0
-20.0
20.0
°C
IS-R
PC65
Compensation start temperature for dynamic
summer set point
30.0
-15.0
PC66
°C
IS-R
PC66
Compensation stop temperature for dynamic
summer set point
60.0
PC65
70.0
°C
IS-R
PC67
10.0
-20.0
20.0
°C
IS-R
PC68
Compensation start temperature for dynamic
winter set point
0.0
-15.0
PC69
°C
IS-R
PC69
Compensation stop temperature for dynamic
winter set point
30.0
PC68
70.0
°C
IS-R
PC70
Function limit management:
0 = Only heat pump
1 = Activation of auxiliary output as
alternative to the heat pump
2 = Activation of auxiliary output and heat
pump
0
0
2
IS-R
PC71
Function limit set point
-7.0
-30.0
30.0
°C
IS-R
PC72
Function limit differential
4.0
0.1
10.0
°C
IS-R
PC80
Enabling of control on request
No (0)
No (0)
Yes (1)
IS-R
PC81
Set point for summer control on request
15.0
-15.0
70.0
°C
IS-R
PC82
Set point for winter control on request
45.0
-15.0
70.0
°C
IS-R
PC83
Differential for summer control on request
4.0
0.1
10.0
°C
IS-R
PC84
Differential for winter control on request
4.0
0.1
10.0
°C
IS-R
PC85
Delay interval for control on request
5
0
999
Sec.
IS-R
CONDENSER PARAMETERS
PF02
It gives the choice to enable fan regulation
only if at least one compressor is ON.
No (0)
No (0)
Yes (1)
IS-F
PF03
It sets whether or not fans must switch OFF
during defrosting cycles.
No (0)
No (0)
Yes (1)
IS-F
PF07
Min. time which must elapse between the
start-ups of two different fans.
10
0
999
Sec.
IS-F
PF08
Min. time which must elapse between the
shutdowns of two different fans.
20
0
999
Sec.
IS-F
PF10
Forcing of fans in case of condensing probe
alarm
0.0
0.0
100.0
%
IS-F
PF11
Condensing regulation set point for summer
operation (chiller)
20.0
5.0
45.0
Bar
IS-F
PF12
Linear regulation band for condensation in
summer operation (chiller)
12.0
0.1
15.0
Bar
IS-F
PF13
Enabling of forcing to maximum in summer
operation
Yes (1)
No (0)
Yes (1)
IS-F
PF14
Max. forcing enabling set point in summer
operation (chiller)
26.0
15.0
45.0
Bar
IS-F
PF15
Disabling differential for max. forcing in
summer operation (chiller)
2.0
0.1
5.0
Bar
IS-F
PF21
Condensing regulation set point in winter
operation (heat pump)
9.0
0.5
15.0
Bar
IS-F
PF22
Linear regulation band for condensation in
winter operation (heat pump)
2.0
0.1
15.0
Bar
IS-F
PF23
Enabling of forcing to maximum in winter
operation (inverter)
Yes (1)
No (0)
Yes (1)
IS-F
PF24
Max. forcing activation set point in winter
operation (heat pump, inverter)
3.2
0.5
20.0
Bar
IS-F
PF25
Max. forcing de-activation differential in
0.5
0.1
5.0
Bar
IS-F