EVCO c-pro nano CHIL User Manual

Page 76

Advertising
background image

C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 76

PH09

It enables the start-up/shutdown of the
machine by supervisor.

No (0)

No (0)

Yes (1)

IS-V

PH10

It enables the change of summer/winter
operating mode via supervisor.

No (0)

No (0)

Yes (1)

IS-V

PH11

Card Modbus address

1

1

247

IS-V

PH12

Card communication baud rate (1=2400,
2=4800, 3=9600, 4=19200)

3

1

4

IS-V

PH13

Modbus parity (0=none, 1=Odd, 2=Even)

2

0

2

IS-V

PH14

Modbus stop bit (0=1 bit, 1=2 bits)

0

0

1

IS-V

PH15

It resets the factory-set parameter defaults.

No (0)

No (0)

Yes (1)

IS-V

Wait for the 0
value to be re-
read at the end of
resetting.

PH16

It sets the logic used for the inverting valve.
0: NO – Normally open
1: NC – Normally closed

NO

NO (0)

NC (1)

IS-V

PH17

It sets the logic of digital inputs used in alarm
management.
0: NO – Normally open
1: NC – Normally closed

NC

NO (0)

NC (1)

IS-V

PH18

It sets the logic of the relay used for alarms.
0: NO – Normally open
1: NC – Normally closed

NO

NO (0)

NC (1)

IS-V

PH19

It sets the logic of the digital input used for the
summer/winter commutation.
0: NO – Normally open
1: NC – Normally closed

NO

NO (0)

NC (1)

IS-V

PH20

It sets the logic of the digital input used for
flow control.
0: NO – Normally open
1: NC – Normally closed

NO

NO (0)

NC (1)

IS-V

PH21

It sets the enabling of the probe for ambient
temperature detection (incoming).

Yes (1)

No (0)

Yes (1)

IS-V

PH22

It sets the enabling of the probe for delivery
temperature detection (outgoing) in Circuit #
1.

Yes (1)

No (0)

Yes (1)

IS-V

PH23

It sets the enabling of the probe for delivery
temperature detection (outgoing) in Circuit #
2.

Yes (1)

No (0)

Yes (1)

IS-V

PH24

It sets the enabling of the probe for external
temperature detection.

No (0)

No (0)

Yes (1)

IS-V

PH25

It sets the enabling of the secondary set point
function from digital input.

No (0)

No (0)

Yes (1)

IS-V

PH26

It sets the enabling of the secondary set point
function by a supervisor.

No (0)

No (0)

Yes (1)

IS-V

PH27

It sets the enabling of the dynamic set point
function.

No (0)

No (0)

Yes (1)

IS-V

PH29

It sets the logic of the digital inputs used for
compressor activation:
0: NO – Normally open
1: NC – Normally closed

NO

NO (0)

NC (1)

IS-V

PH31

It sets the type of refrigerant used
(temperature-pressure conversion).
0: No refrigerant
1: R22
2: R134a
3: R404A
4: R407C
5: R410A
6: R507

3

R404A

0

6

IS-V

PH32

It sets the temperature measurement unit:

0 (°C)

0

1

IS-V