C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 85

6.2.3

Single-circuit water-to-water units

PG01 = 1
Single-circuit

PG00 = 5
Water-to-water chiller

PG00 = 6
Water-to-water chiller + heat pump

Analogue inputs

AI 1

(NTC)

Inlet water temperature

Inlet water temperature

AI 2

(NTC)

Outlet water temperature

Outlet water temperature

AI 3

(NTC / 4..20 mA)

Condensing pressure/temperature

Condensing pressure/temperature

AI 4

(NTC / 4.20 mA / DI)

Used as DI 6

Used as DI 6

Digital inputs

DI 1

High-pressure pressure switch

High-pressure pressure switch

DI 2

Thermal overload switch compressor # 1

Thermal overload switch compressor # 1

DI 3

Thermal overload switch compressor # 2

Thermal overload switch compressor # 2

DI 4

Flow meter

Flow meter

DI 5

Thermal overload switch pump # 1

Thermal overload switch pump # 1

DI 6 (*)

Low-pressure pressure switch

Low-pressure pressure switch

Digital outputs

DO 1

Circulating pump

Circulating pump

DO 2

Compressor # 1

Compressor # 1

DO 3

Compressor # 2

Compressor # 2

DO 4

-

Circuit inverter valve

DO 5

Anti-frost heating coil

Anti-frost heating coil

DO 6

General alarm

General alarm

Analogue outputs

AO 1

(PWM)

-

-

AO 2

(0..10 V / 4..20 mA)

Condensing valve control

Condensing valve control

AO 3

(0..10 V / 4..20 mA)

-

-


By selecting these units, default values for parameters PC11=1 and PH44=1 are automatically set,
while a “0” value is set for all input/output position parameters not specified in this configuration.

(*) Digital input derived from analogue input (parameter PH44).