2 connection layout of c-pro exp micro, C-pro micro exp controller – EVCO c-pro nano CHIL User Manual
Page 53
![background image](/manuals/675457/53/background.png)
C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 53
2.11.2
Connection layout of C-PRO EXP MICRO
The connection layout of C-PRO EXP MICRO is shown below, with related tables explaining the
meaning of inputs and outputs.
4
2
3
5
7
6
9
8
11
2
2
1
1
12
3
3
1
connector # 1
K7
K8
K9
K10
K11
K12
16
8
15
7
14
6
13
5
12
4
11
3
10
2
9
1
connector # 2
connector # 3
connector # 5
m
a
x
.
3
A
m
a
x
.
3
A
m
a
x
.
3
A
m
a
x
.
4
A
m
a
x
.
3
A
C-PRO
MICRO
EXP
CONTROLLER
Connector 1
: Connection for relay outputs
Conn.
Label
Description
C1-1
DO7
Normally open contact relay # 7
C1-2
COMMON DO7
Common relay # 7
C1-3
DO8
Normally open contact relay # 8
C1-4
COMMON DO8
Common relay # 8
C1-5
DO9
Normally open contact relay # 9
C1-6
COMMON DO9
Common relay # 9
C1-7
DO10
Normally open contact relay # 10
C1-8
COMMON 1
Common relays # 10, 11
C1-9
DO11
Normally open contact relay # 11
C1-10
Not in use
C1-11
DO12
Normally open contact relay # 12
C1-12
COMMON DO12
Common relay # 12
Connector 2
: Connector for low-voltage signals
Conn.
Label
Description
C2-1
12 V AC (power
supply)
Instrument power supply (12 V AC/DC)
C2-2
Not connected
Not connected
C2-3
GND
Common analogue and digital inputs
C2-4
GND
Common analogue and digital inputs
C2-5
AI8
Analogue input # 8 (4-20 mA transducer)
C2-6
AI7
Analogue input # 7 (4-20 mA transducer)
C2-7
AI6
Analogue input # 6 (NTC probe)
C2-8
AI5