C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 69

5.1

List of Configuration Parameters

Code

Parameter Description

Default

Min.

Max.

M.U.

Menu

Notes

USER PARAMETERS

ModE

It sets the operating mode:
0: CooL, (Chiller/summer)
1: hEAt (Heat pump/winter)

0

0

1

UT

Modifiable only
if the units is a
chiller + heat
pump:
(PG00=2,4,6,8,1
0 e PG08=0)

SPC1

It sets the value of the summer set point
(chiller)

8.5

PC21

PC22

°C

UT

SSC1

It sets the offset value for the utilisation of the
secondary summer set point.

0.0

-20.0

20.0

°C

UT

SPH1

It sets the value of the winter set point (heat
pump).

44.0

PC23

PC24

°C

UT

SSH1

It sets the offset value for the utilisation of the
secondary summer set point.

0.0

-20.0

20.0

°C

UT

PSd1

It modifies the password at User level.

0

-999

9999

UT

MAINTENANCE PARAMETERS

PM00

It sets – in tens – the maximum number of
operating hours of compressors. When this
limit is exceeded, the connected alarm is
triggered.

2000

0

9999

hours

x

10

MA-F

PM01
PM02
PM03
PM04
PM05
PM06

It shows – in tens – the number of operating
hours of compressors. One parameter for each
compressor.

0

0

9999

hours

x

10

MA-F

PM30

It sets – in tens – the maximum number of
operating hours of pumps / delivery fan. When
this limit is exceeded, the connected alarm is
triggered.

2000

0

9999

hours

x

10

MA-F

PM31

It shows – in tens – the number of operating
hours of the first pump / delivery fan.

0

0

9999

hours

x

10

MA-F

PM32

It shows – in tens – the number of operating
hours of the second pump.

0

0

9999

hours

x

10

MA-F

PM40

It sets – in tens – the maximum number of
operating hours of fans. When this limit is
exceeded, the connected alarm is triggered.

2000

0

9999

hours

x

10

MA-F

PM41

It shows – in tens – the number of operating
hours of the first fan or of the inverter in
Circuit # 1.

0

0

9999

hours

x

10

MA-F

PM42

It shows – in tens – the number of operating
hours of the second fan or of the inverter in
Circuit # 2.

0

0

9999

hours

x

10

MA-F

PM91

It sets the date (year) when the last plant
maintenance was carried out.

2007

2007

2060

MA-

F

«

PM92

It sets the date (month) when the last plant
maintenance was carried out.

1

1

12

MA-F

PM93

It sets the date (day) when the last plant
maintenance was carried out.

1

1

31

MA-F

PM11
PM12

It enables the manual/automatic operation of
the compressor.

0

0

1

MA-M