C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 83

6.2

Unit Type


With the machine in OFF status, using the PG00 parameter from the CONSTRUCTOR menu (CoSt
-> ConF
), it is possible to select the unit type to be used, and, via the PG01 parameter, it is then
possible to set up the number of circuits. Based on parameter values, several defaults are loaded for
the positions of inputs and outputs. Regulation and other parameters corresponding to the various
functions must be manually modified according to user requirements.
Managed machines are listed below, together with their respective input and output configurations.

SINGLE-CIRCUIT VERSIONS (PG01=1)

6.2.1

Single-circuit air-to-air units

PG01 = 1
Single-circuit

PG00 = 1
Air-to-air chiller

PG00 = 2
Air-to-air chiller + heat pump

Analogue inputs

AI 1

(NTC)

Ambient air temperature

Ambient air temperature

AI 2

(NTC)

Delivery air temperature

Delivery air temperature

AI 3

(NTC / 4..20 mA)

Condensing pressure

Condensing pressure

AI 4

(NTC / 4.20 mA / DI)

Used as DI 6

Used as DI 6

Digital inputs

DI 1

High-pressure pressure switch

High-pressure pressure switch

DI 2

Thermal overload switch compressor # 1

Thermal overload switch compressor # 1

DI 3

Thermal overload switch compressor # 2

Thermal overload switch compressor # 2

DI 4

Air-flow differential pressure switch

Air-flow differential pressure switch

DI 5

Recirculating fan thermal switch

Recirculating fan thermal switch

DI 6 (*)

Low-pressure pressure switch

Low-pressure pressure switch

Digital outputs

DO 1

Recirculating fan

Recirculating fan

DO 2

Compressor # 1

Compressor # 1

DO 3

Compressor # 2

Compressor # 2

DO 4

-

Circuit inverter valve

DO 5

-

Defrosting-support heating coil

DO 6

General alarm

General alarm

Analogue outputs

AO 1

(PWM)

Condensing fan

Condensing fan

AO 2

(0..10 V / 4..20 mA)

-

-

AO 3

(0..10 V / 4..20 mA)

-

-


By selecting these units, default values for parameters PC11=1 and PH44=1 are automatically set,
while a “0” value is set for all input/output position parameters not specified in this configuration.

(*) Digital input derived from analogue input (parameter PH44).