EVCO c-pro nano CHIL User Manual

Page 124

Advertising
background image

C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 124

The alarm is initially auto-resetting, unless it exceeds a given number of events within one hour
(PA14), in which case it becomes a manual-reset alarm, which can be reset if in the meantime
pressure has risen above the minimum threshold by a certain differential value.

-

PA11 = Low-pressure alarm set point

-

PA12 = Low-pressure alarm differential

-

PA13 = Low-pressure alarm by-pass time

-

PA14 = Maximum number of auto-reset low-pressure alarms


In the presence of low temperatures of external air, intake pressure could fall below the minimum-
pressure threshold, thus inhibiting compressor start-up. In such a situation, it is possible to activate
a control, which shifts the alarm-control threshold to a higher value for a given interval from start-
up of the first compressor, leaving nevertheless in place all protection devices and pre-start checks.

-

PA16 = Low-pressure control enable at low external temperature

-

PA17 = Low-pressure alarm set point at low external temperature

-

PA18 = Low-pressure alarm differential at low external temperature

-

PA19 = Low-pressure alarm control duration at low external temperature


This control can only be enabled in heat-pump operating mode.

6.16.5

Low start-up pressure alarm

In a low-pressure condition (pressure switch or transducer-induced) and in the impossibility to
activate any of the compressors at the request of the same, there is a Low-pressure start-up alarm
AL51
(and AL52 for Circuit # 2). This is an auto-reset alarm, and thus should disappear, unless
there is a leak of Freon® gas from the circuit.
At compressor shutdown following a low-pressure alarm, this alarm is delayed by a given interval
PA20, to give the refrigerating circuit the chance to enable compressor start-up.



Advertising
This manual is related to the following products: