C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 118


6.12.3

Defrosting heating coil

On heat pumps which do not possess the necessary thermal inertia of the recirculation mass (e.g.
air-to-air units), defrosting causes a rapid fall in ambient temperature, and it is therefore advisable –
to ensure greater comfort – to provide for the control of a defrosting-support heating coil.

6.13

Anti-frost management / Chilling-support heating coils


On air-to-water or water-to-water machines, anti-frost control is active even when the machine is
switched OFF, whereas on air-to-air machines heating coils only intervene when the machine is
ON.
Two thresholds are provided for, with their related differential: one is used to activate the heating
coils and the other one to signal the alarm and stop compressors within the associated circuit.
If the anti-frost alarm should persist for the duration of the Pump operation time at low temperature
PP10
, the pump will be switched OFF until the next alarm reset.
In the case of anti-frost, in OFF status, only the heating coils are activated, whereas the alarm is not
notified.
In order to enable the heating coils, in addition to setting the associated parameter (Pr01=1), it is
also necessary to set from the CoSt->HArd menu the positions (HA02, HA03) of the digital outputs
corresponding to the two heating coils in use.