16 pressure alarm control – EVCO c-pro nano CHIL User Manual

Page 123

Advertising
background image

C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 123

6.16

Pressure Alarm Control

6.16.1

Management of high-pressure pressure-switch alarm

Via a digital input connected to an external pressure switch, it is possible to monitor an excess of
maximum condensing pressure. The high-pressure alarm AL11 (and AL12 for Circuit # 2) causes
the immediate stopping of the refrigerating circuit, also shutting down any compressors which may
be ON, and inhibiting the start-up of others.
This alarm is only detected when the machine is switched ON.
This is a manual-reset alarm.

6.16.2

Management of high-pressure transducer alarm

If condensing pressure exceeds a given threshold, a high-pressure alarm AL31 (and AL32 for
Circuit # 2) is generated. The alarm causes the immediate stopping of the refrigerating circuit, also
shutting down any compressors which may be ON, and inhibiting the start-up of others.
This alarm is only detected when the machine is switched ON.
This is a manual-reset alarm and it can be reset if in the meantime pressure has fallen below the
maximum threshold of a given differential value.

-

PA21 = High-pressure alarm set point

-

PA22 = High-pressure alarm differential


6.16.3

Management of low-pressure pressure-switch alarm (chiller mode)

Via a digital input connected to an external pressure switch, it is possible to monitor the presence of
a minimum intake pressure in the refrigerating circuit. The low-pressure alarm AL41 (and AL42 for
Circuit # 2) causes the immediate stopping of the refrigerating circuit, also shutting down any
compressors which may be ON, and inhibiting the start-up of others.
At start-up of the first compressor, the alarm is delayed for a given interval, to enable the
compressors to take the refrigerating circuit to full pressure.
The alarm is initially auto-resetting, unless it exceeds a given number of events within one hour
(PA14), in which case it becomes a manual-reset alarm.

-

PA13 = Low-pressure alarm by-pass time

-

PA14 = Maximum number of auto-reset low-pressure alarms


If, with the machine switched ON and in the presence of a request for chill from the
thermoregulator, low pressure is detected, compressor start-up is inhibited and a Start-up low-
pressure alarm AL21
(and AL22 for Circuit # 2) is displayed. The purpose of this condition is to
inhibit compressor start-up in the absence of Freon® gas in the circuit (there could be a refrigerant
leak from the piping system).

6.16.4

Management of low-pressure transducer alarm (heat pump mode)

If intake pressure falls below a given threshold, a low-pressure alarm AL41 (and AL42 for Circuit #
2) is generated. The alarm causes the immediate stopping of the refrigerating circuit, also shutting
down any compressors which may be ON, and inhibiting the start-up of others.
At start-up of the first compressor, the alarm is delayed for a given interval, to enable the
compressors to take the refrigerating circuit to full pressure.

Advertising
This manual is related to the following products: