C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 87
6.2.5
Single-circuit motocondensing water-based units
PG01 = 1
Single-circuit
PG00 = 9
Motocondensing, water-based
PG00 = 10
Motocondensing, water-based, with cycle
inversion
Analogue inputs
AI 1
(NTC)
-
-
AI 2
(NTC)
-
-
AI 3
(NTC / 4..20 mA)
Condensing water pressure/temperature
Condensing water pressure/temperature
AI 4
(NTC / 4.20 mA / DI)
Used as DI 6
Used as DI 6
Digital inputs
DI 1
Flow meter
Flow meter
DI 2
Thermal overload switch compressor # 1
Thermal overload switch compressor # 1
DI 3
Thermal overload switch compressor # 2
Thermal overload switch compressor # 2
DI 4
Compressor 1
st
step control
Compressor 1
st
step control
DI 5
Compressor 2
nd
step control
Compressor 2
nd
step control
DI 6 (*)
Low-pressure pressure switch
Low-pressure pressure switch
Digital outputs
DO 1
Circulating pump
Circulating pump
DO 2
Compressor # 1
Compressor # 1
DO 3
Compressor # 2
Compressor # 2
DO 4
-
Circuit inverter valve
DO 5
-
-
DO 6
General alarm
General alarm
Analogue outputs
AO 1
(PWM)
-
-
AO 2
(0..10 V / 4..20 mA)
Condensing valve control
Condensing valve control
AO 3
(0..10 V / 4..20 mA)
-
-
By selecting these units, default values for parameters PC11=2 and PH44=1 are automatically set,
while a “0” value is set for all input/output position parameters not specified in this configuration.
(*) Digital input derived from analogue input (parameter PH44).