C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL
Pag. 127
The parameters referred to this function are the following:
-
PC64 = Maximum dynamic offset for summer operation (chiller)
-
PC65 = Compensation start temperature for dynamic summer set point
-
PC66 = Compensation stop temperature for dynamic summer set point
With offsets greater than zero, behaviour is as follows:
The parameters referred to this function are the following:
-
PC67 = Maximum dynamic offset for winter operation (heat pump)
-
PC68 = Compensation-start temperature for dynamic winter set point
-
PC69 = Compensation- stop temperature for dynamic winter set point
6.17.5
Forced shutdown
This function enables the forced shutdown of all compressors, when outlet temperature falls below
the Summer forced-shutdown set point (in the case of chiller operation), or exceeds the Winter
forced-shutdown set point (in the case of heat-pump operation). Compressors can only be restarted
when the temperature crosses the set point once again.
-
PC35 = Forced-shutdown enable
-
PC36 = Summer forced-shutdown set point
-
PC37 = Winter forced-shutdown set point
On MOTOCONDENSING units and with PC11=2, this function is disabled.
SP + PC67
SP
Set Point
Ext. T
PC68
PC69
SP
SP + PC64
Set Point
Ext. T
PC65
PC66