C-PRO NANO CHIL AND C-PRO MICRO CHIL – APPLICATION MANUAL

Pag. 127

The parameters referred to this function are the following:

-

PC64 = Maximum dynamic offset for summer operation (chiller)

-

PC65 = Compensation start temperature for dynamic summer set point

-

PC66 = Compensation stop temperature for dynamic summer set point


With offsets greater than zero, behaviour is as follows:


The parameters referred to this function are the following:

-

PC67 = Maximum dynamic offset for winter operation (heat pump)

-

PC68 = Compensation-start temperature for dynamic winter set point

-

PC69 = Compensation- stop temperature for dynamic winter set point



6.17.5

Forced shutdown

This function enables the forced shutdown of all compressors, when outlet temperature falls below
the Summer forced-shutdown set point (in the case of chiller operation), or exceeds the Winter
forced-shutdown set point
(in the case of heat-pump operation). Compressors can only be restarted
when the temperature crosses the set point once again.

-

PC35 = Forced-shutdown enable

-

PC36 = Summer forced-shutdown set point

-

PC37 = Winter forced-shutdown set point


On MOTOCONDENSING units and with PC11=2, this function is disabled.

SP + PC67

SP

Set Point

Ext. T

PC68

PC69

SP

SP + PC64

Set Point

Ext. T

PC65

PC66