AC Power Supplies

ReFlex Power™

4-74

M380056-01 Rev K

15. Wait for AC current to stabilize. Measure the output current using the AC meter.

Enter the measured current:

CAL<n>:OUTP:FREQ:CURR2 <value-2>

16. Set the output frequency to 1000Hz

SOUR<n>:FREQ 1000

17. Wait for AC current to stabilize. Measure the output current using the AC meter.

Enter the measured current:

CAL<n>:OUTP:FREQ:CURR3 <value-3>

18. Set the output frequency to 2000Hz:

SOUR<n>:FREQ 2000

19. Wait for AC current to stabilize. Measure the output current using the AC meter.

Enter the measured current:

CAL<n>:OUTP:FREQ:CURR4 <value-4>

20. Set the output frequency to 3000Hz:

SOUR<n>:FREQ 3000

21. Wait for AC current to stabilize. Measure the output current using the AC meter.

Enter the measured current:

CAL<n>:OUTP:FREQ:CURR5 <value-5>

22. Set the output frequency to 4000Hz:

SOUR<n>:FREQ 4000

23. Wait for AC current to stabilize. Measure the output current using the AC meter.

Enter the measured current:

CAL<n>:OUTP:FREQ:CURR6 <value-6>

24. Set the output frequency to 5000Hz:

SOUR<n>:FREQ 5000

25. Wait for AC current to stabilize. Measure the output current using the AC meter.

Enter the measured current:

CAL<n>:OUTP:FREQ:CURR7 <value-7>

26. Perform the voltage calibration:

CAL<n>:OUTP:FREQ:CALC

27. Send the system error query command to make sure calibration was successful:

SYST:ERR?