2 canopen interface, 3 can-bus cable, Bus cable – BECKHOFF AX2000 CANopen communication profile User Manual

Page 11: Cable length, Termination resistance, Canopen interface, Can-bus cable, Installation / setup

Advertising
background image

2.2

CANopen interface

The interface for connection to the CAN-bus (default : 500 kBaud). The interface is at the same
electrical potential as the RS232 interface. The analog setpoint inputs can still be used.

We can supply special clamp-sleeve connectors, that can easily be made up for bus operation.
In addition, an adapter can be used for the option slot (Option -2CAN-), which provides options for
pass-through wiring and the attachment of 120

W termination resistors. The pin assignments corre-

spond to ISO 11898 (CAN).

For the purpose of equipotential bonding, AGND must be connected to the controller! For
additional information, see the servo amplifier Product Manual.

2.3

CAN-bus cable

In accordance with ISO 11898 you should use a bus cable with a characteristic impedance of 120

W.

The usable cable length for reliable communication is reduced as the transmission rate is increa-
sed. The following values that we have measured can be used as a guide. They should not, howe-
ver, be interpreted as limiting values:
Cable data:

characteristic impedance

100 ... 120

W

cable capacitance

max. 60 nF/km

lead resistance (loop)

159.8

W/km

Cable length, dependent on the transmission rate

Transmission rate: kbit/s

Max. cable length: m

1000

20

500

70

250

115

Longer transmission distances may be achieved with a lower cable capacitance (max. 30 nF/km)
and lower lead resistance (loop, 115

W/km).

(characteristic impedance 150 ± 5

W Þ termination resistance 150 ± 5W).

For EMC reasons, the SubD connector housing must fulfill the following requirements:

metal or metallic housing

provision for connecting the cable shielding in the housing, with a large contact area.

The BECKHOFF company can supply special clamp-sleeve connectors (Order No. DE-90650), that
can easily be made up for bus operation.
In addition, an adapter can be used for the option slot (Option -2CAN-, Order No. 101174), which
provides options for pass-through wiring and the attachment of 120

W termination resistors. The pin

assignments correspond to the CANopen standard DS 301.

CANopen for AX2000/2500

11

BECKHOFF

07/2007

Installation / Setup

AX2000/2500

Advertising