2 object description, 1800-1803h, 1a00-1a03h – BECKHOFF AX2000 CANopen communication profile User Manual

Page 49: 2a00-2a03h, Inhibit time, Object description, Canopen drive profile

Advertising
background image

4.3.2.2

Object Description

4.3.2.2.1

Object 1800-1803h: 1st-4th Transmit-PDO communcation param. (DS301)

Sub-index

Description

00

h

number of entries

01

h

PDO COB-ID *

02

h

transmission type

03

h

inhibit time **

04

h

CMS priority group

*

After selecting a PDO higher than 2A00

h

to 2A03

h

, here you can define the COB-identifier that the amplifier

responds to (if a different setting is required from the default value).

**

This sets a waiting time that must be observed after a PDO has been transmitted, before a new transmission

can be made (only important for event-triggered PDOs).

4.3.2.2.2

Object 1A00-1A03h: 1st-4th Transmit-PDO mapping parameter (DS301)

Sub-index

Description

00

h

number of configured Objects

01

h

... 08

h

description of the configured Objects

4.3.2.2.3

Object 2A00-2A03h: 1st-4th Transmit-PDO select (DS301)

This Object is used to select a predefined transmit-PDO.
The Objects 1800

h

to 1803

h

1

st

to 4

th

transmit-PDO parameter and 1A00

h

to 1A03

h

1

st

to 4

th

trans-

mit-PDO mapping can then be used to define the characteristics of this PDO.

This Object enables variable mapping of predefined PDOs. The possible PDOs for selection are lis-
ted in the table in Chapter 4.3.2.

Index

2A00

h

to 2A03

h

Name

1

st

to 4

th

transmit-PDO select

Object code

VAR

Data type

UNSIGNED8

Access

rw

PDO mapping

not possible

Value range

0 ... 255

Default value

0

CANopen for AX2000/2500

49

BECKHOFF

07/2007

CANopen Drive Profile

Advertising