Beckhoff – BECKHOFF AX2000 CANopen communication profile User Manual

Page 82

Advertising
background image

Sub-index

0A

h

Brief description

speed

Unit

min

-1

Access

ro

PDO mapping

not possible

Data type

INTEGER32

Value range

-(2

31

-1) ... (2

31

-1)

Default value

0

Used to read out the momentary speed measurement.

Sub-index

0B

h

Brief description

heat sink temperature

Unit

°C

Access

ro

PDO mapping

not possible

Data type

INTEGER32

Value range

-(2

31

-1) ... (2

31

-1)

Default value

0

Used to read out the heat sink temperature.

Sub-index

0C

h

Brief description

internal temperature

Unit

°C

Access

ro

PDO mapping

not possible

Data type

INTEGER32

Value range

-(2

31

-1) ... (2

31

-1)

Default value

0

Used to read the internal temperature of the servo amplifier.

Sub-index

0D

h

Brief description

DC-link (DC-bus) voltage

Unit

V

Access

ro

PDO mapping

not possible

Data type

INTEGER32

Value range

-(2

31

-1) ... (2

31

-1)

Default value

0

Used to read out the momentary DC-bus voltage.

Sub-index

0E

h

Brief description

regen power

Unit

W

Access

ro

PDO mapping

not possible

Data type

INTEGER32

Value range

-(2

31

-1) ... (2

31

-1)

Default value

0

Used to read out the momentary regen power.

Sub-index

0F

h

Brief description

I²t loading

Unit

%

Access

ro

PDO mapping

not possible

Data type

INTEGER32

Value range

-(2

31

-1) ... (2

31

-1)

Default value

0

Used to read out the I²t loading.