VS-616G5 Programming Manual

103

When operating several motors with one inverter, install a thermal relay on each motor. In this case, set
parameter L1-01 to “0”.

Setting Range:

0.1 to 20.0 minutes

<1110>

Factory Default:

8.0 minutes

Sets the amount of time that the motor withstands 150% overload, when the motor is operated continu-
ously at rated current. This value should be set according to the overload resistance of motors used.

Notes:

1. If the motor is running at 100% output current or less, the electronic thermal overload relay

will not trip. (continued next page)

2. If the motor is run continuously at 150% output current, the electronic thermal overload relay

will trip after one minute if the motor is started “hot”, and after eight minutes if the motor is
started “cold”.

L2

Power Loss Ridethrough
When momentary power loss occurs, operation can restart automatically, according to the setting of
the following parameters.

Selects whether the inverter stops when power loss is detected or “rides through” a momentary power
loss. When ridethrough operation is selected, speed search starts from the current output frequency.

L1-02 Motor Protection Time Constant

MOL Time Const

B

B

B

B

L2-01 Momentary Power Loss Ridethrough Selection

PwrL Selection

B

B

B

B

Setting

Description

0

Momentary power loss ridethrough is disabled (factory default).
When momentary power loss is detected, a fault contact trips,
stopping the inverter.

1

Momentary power loss ridethrough is enabled, for the time set in
L2-02

. When momentary power loss is detected, a fault contact

does not trip. If power is not restored within the time set in L2-02, a
fault contact trips, stopping the inverter.

Figure 49 Electronic Thermal Overload Curve

min

%

Motor Rated Current (E2-01)

“Cold” Start

“Hot” Start

Operating

Time

10

7

3

1

0.4

0

100

150

200

(when L1-02 = “1.0”)

Section L: Protection Parameters

L1 Motor Overload