VS-616G5 Programming Manual

29

V/f

V/f w/PG Open Loop

Vector

Flux

Vector

B9

Zero Servo
The zero servo function is enabled when the multi-function contact input is set to zero servo command
(H1-__ = “72”). The motor position is then memorized when motor speed feedback is less than the
zero speed level (B2-01).

Setting Range:

0 to 100

Factory Default:

5

Sets the zero-servo position loop gain. When adjusting the gain, the higher the setting, the quicker the
response. However, if the gain is set too high, it can cause overshoot and a possible runaway condition.

Setting Range:

0 to 16383 pulses

Factory Default:

10 pulses

Sets zero servo bandwidth in units of one pulse. During zero servo control, the multi-function contact
output (H2-__ = “33”) is closed until the number of pulses (or bandwidth) is completed. Then the con-
tact output opens.

B9-01 Zero Servo Gain

Zero Servo Gain

-

-

-

A

B9-02 Zero Servo Bandwidth

Zero Servo Count

-

-

-

A

L2-04

Figure 10 Timing Diagram of Energy Saving Function

Fref

B8-02

FWD

Energy

Saving

Command

(Multi-function input

setting = “63”)

Fout

Vout

V/f Pattern × Energy Saving Gain (B8-01)

Figure 11 Zero Servo Position Loop

0

(Position Ref.)

Kp

B9-01

Motor Speed Feedback

Speed Reference

+

-

Motor

Position Deviation

Counter

Section B: Application Parameters

B9 Zero Servo