Section L: Protection Parameters

L2 Power Loss Ridethrough

Setting Range:

0.0 to 2.0s

Factory Default:

Inverter model dependent

Sets the ridethrough time allowed before the inverter trips, after momentary power loss. This setting is
activated when L2-01 is set to “1”. If power is restored within this time, operation restarts automati-
cally. If power is not restored within this time, a fault contact trips, stopping the inverter.

2

Momentary power loss ridethrough is enabled, within the control
logic time, regardless of the time set in L2-02. The control logic
time differs depending on inverter capacity.

L2-02

Momentary Power Loss Ridethrough Time

PwrL RideThru t

B

B

B

B

Setting

Description