VS-616G5 Programming Manual

Setting Range:

0.0 to 400.0Hz

Factory Default:

0.0Hz

After the multi-function contact input for energy-saving operation closes (H1-__, setting: “63”), the
output voltage is decreased when the output frequency reaches the energy-saving starting frequency.
This feature is only enable by multi-function contact input.

.

This parameter is used to select if Automatic Energy Saving Mode is to be on or off. A multi-function
contact input is not required to activate Automatic Energy Saving Mode. This mode of operation auto-
matically searches for the optimum motor voltage required to save energy. This function is separate
and not to be confused with parameters B8-01 and B8-02. The energy saving mode that utilizes B8-01
and B8-02 requires a multi-function input to be activated for operation. This Automatic Energy Sav-
ing Mode selection does not require a multi-function input to activate operation.

Setting Range:

0 to 10.0

Factory Default:

0.7

The output voltage during energy-saving operation is the product of the normal V/f settings (El-03 to
E1-10) and the energy saving gain. The output voltage decreases and recovers according to the Energy-
Saving Control Time Constant B8-05
. As the energy saving gain increases, the output voltage
increases also.

Note: When the control mode A1-02=3, the default factory setting becomes 1.0

Setting Range:

0.00 to 10.00

Factory Default:

0.50

Parameter B8-05 sets the response time for the Automatic Energy Saving function.
Decreasing the Energy Control Time-Constant, will cause the response to become quicker; however,
instability may occur if this is decreased too much.
Note: When control mode A1-02=3, the default factory setting becomes 0.01.

B8-02 Energy Saving Starting Frequency

Energy Save Freq

A

A

-

-

B8-03 Automatic Energy Saving

<1110>

Energy Save Sel

-

-

A

A

Setting

Description

0

Disabled (factory default)
Energy saving mode will not be activated under light loads.

1

Enabled
The energy saving mode will be activated under light loads.

B8-04 Energy Saving Control Gain

Energy Save Gain

-

-

A

A

B8-05 Energy Control Time-Constant

Energy Save F. T

-

-

A

A

Section B: Application Parameters

B8 Energy Savings