· Coast to Stop with Timer 1 (B1-03 = “3 ”)

After a stop command is given, a run command is not accepted while the coast to stop timer elapses
(same as Decel 1). After the timer runs out, another run command must be given for the inverter to
begin acceleration. This stopping method is disabled during flux vector control.

A “reverse run disabled” setting does not allow a reverse run command from the control circuit termi-
nal or the digital operator. This setting is used in applications where a reverse run command is undesir-
able.

B1-04 Prohibition of Reverse Operation

Reverse Oper

B

B

B

B

Setting

Description

0

Reverse run enabled (factory default)

1

Reverse run disabled

Output Frequency

Coasting

Decel Time 1
(C1-02)

Accel Time 1
(C1-01)

Time

ON

ON

ON

FWD (REV)

Run Command

Run Command Disabled

Figure 4 Stopping Method - Coast to Stop w/ Timer

Section B: Application Parameters

B1 Sequence