Yaskawa VS-616G5 Series Revision F Programming Manual User Manual
Page 46

V/f
V/f w/PG Open Loop
Vector
Flux
Vector
46
VS-616G5 Programming Manual
Setting Range:
0.0 to 400.0Hz
Factory Default:
0.0Hz
The jog frequency reference can be set in this parameter. Depress the JOG key on the digital
operator, or close terminal 7, to use this function. The jog command always has priority over
other reference commands. When using the multi-step speed references, change the jog com-
mand from terminal 7 to terminal 8 (H1-06 = “6”).
Note:
Setting units for D1-01 to D1-09 are dependent upon the setting of digital operator display
mode (O1-03). Possible setting units include Hz, percentage, RPM or engineering units. See
section O1, Monitor Selection, on page 120 for more details.
D1-09 Jog Frequency Reference
JOG Reference
Q
Q
Q
Q
Multi-step Speed Ref. 1
Frequency
Reference
FWD (REV) Run/Stop
(Terminal 5)
Multi-step Speed Ref. 2
(Terminal 6)
D1-04
40.0Hz
D1-01
10.0Hz
D1-02
20.0Hz
D1-03
30.0Hz
ON
ON
ON
ON
Figure 24 Multi-step Speed Operation - Timing Diagram
Multi-step Speed Ref. 3
(Terminal 7)
Jog Ref.
(Terminal 8)
ON
ON
ON
ON
ON
D1-05
45.0Hz
D1-06
50.0Hz
D1-07
55.0Hz
D1-08
60.0Hz
D1-09
6.0Hz
Time
Section D: Reference Parameters
D1 Preset References